User’s Manual EM11A015B
intelligent Touch Manager
46
•
R/C Prohibition Tab
Enables/disables remote controller of the indoor unit, Ventilator, Chiller and area.
Change settings by selecting the relevant check boxes.
(1)
(2)
(3)
(1)
Start/Stop
Sets up whether starting/stopping the management point from the remote controller will be
enabled or disabled.
Permitted
: Enabled.
Stop Only
: Only stopping is enabled.
Prohibited
: Disabled.
In the case of the system with Hydrobox, choosing “Stop Only” or “Prohibited” makes the
water heater to operate as “Permitted”.
NOTE
(2)
Operation Mode
Sets up whether changing the operation mode from the remote controller will be enabled or disabled.
Permitted
: Enabled.
Prohibited
: Disabled.
(3)
Setpoint
Sets up whether changing the management points’ setpoint from the remote controller will be
enabled or disabled.
Permitted
: Enabled.
Prohibited
: Disabled.
In the case of the system with Hydrobox, the storage water setpoint can be changed even when “Prohibited” is selected.
NOTE