Functions
2.26 Additional Functions
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
471
Number of automatic reclosing commands
If the device is equipped with the integrated automatic reclosure, the automatic close commands are also
counted, separately for reclosure after 1-pole tripping, after 3-pole tripping as well as separately for the first re-
closure cycle and other reclosure cycles.
Interrupted currents
Furthermore, for each trip command the interrupted current for each pole is acquired, output in the trip log and
accumulated in a memory. The maximum interrupted current is stored as well. The indicated measured values
are indicated in primary values.
Transmission statistics
In 7SD5 the protection communication is registered in statistics. The delay times of the information between
the devices via interfaces (run and return) are measured steadily. The values are kept stored in the Statistics
folder. The availability of the transmission media is also reported. The availability is indicated in % / min and
% / h. This enables an evaluation of the transmission quality.
If GPS synchronization is configured, the transmission times for each direction and each protection data inter-
face are regularly measured and indicated as long as GPS synchronization is intact.
2.26.3.2 Information List
No.
Information
Type of In-
formation
Comments
1000
# TRIPs=
VI
Number of breaker TRIP commands
1001
TripNo L1=
VI
Number of breaker TRIP commands L1
1002
TripNo L2=
VI
Number of breaker TRIP commands L2
1003
TripNo L3=
VI
Number of breaker TRIP commands L3
1027
Σ
IL1 =
VI
Accumulation of interrupted current L1
1028
Σ
IL2 =
VI
Accumulation of interrupted current L2
1029
Σ
IL3 =
VI
Accumulation of interrupted current L3
1030
Max IL1 =
VI
Max. fault current Phase L1
1031
Max IL2 =
VI
Max. fault current Phase L2
1032
Max IL3 =
VI
Max. fault current Phase L3
2895
AR #Close1./1p=
VI
No. of 1st AR-cycle CLOSE commands,1pole
2896
AR #Close1./3p=
VI
No. of 1st AR-cycle CLOSE commands,3pole
2897
AR #Close2./1p=
VI
No. of higher AR-cycle CLOSE commands,1p
2898
AR #Close2./3p=
VI
No. of higher AR-cycle CLOSE commands,3p
7751
PI1 TD
MV
Prot.Interface 1:Transmission delay
7752
PI2 TD
MV
Prot.Interface 2:Transmission delay
7753
PI1A/m
MV
Prot.Interface 1: Availability per min.
7754
PI1A/h
MV
Prot.Interface 1: Availability per hour
7755
PI2A/m
MV
Prot.Interface 2: Availability per min.
7756
PI2A/h
MV
Prot.Interface 2: Availability per hour
7875
PI1 TD R
MV
Prot.Interface 1:Transmission delay rec.
7876
PI1 TD S
MV
Prot.Interface 1:Transmission delay send
7877
PI2 TD R
MV
Prot.Interface 2:Transmission delay rec.
7878
PI2 TD S
MV
Prot.Interface 2:Transmission delay send
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...