Appendix
A.7 Settings
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
686
302
CHANGE
Change Group
Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A
Change to Another Setting
Group
402A
WAVEFORMTRIGGER
Osc. Fault Rec.
Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup
Waveform Capture
403A
WAVEFORM DATA
Osc. Fault Rec.
Fault event
Pow.Sys.Flt.
Fault event
Scope of Waveform Data
410
MAX. LENGTH
Osc. Fault Rec.
0.30 .. 5.00 sec
2.00 sec
Max. length of a Waveform
Capture Record
411
PRE. TRIG. TIME
Osc. Fault Rec.
0.05 .. 0.50 sec
0.25 sec
Captured Waveform Prior to
Trigger
412
POST REC. TIME
Osc. Fault Rec.
0.05 .. 0.50 sec
0.10 sec
Captured Waveform after Event
415
BinIn CAPT.TIME
Osc. Fault Rec.
0.10 .. 5.00 sec;
∞
0.50 sec
Capture Time via Binary Input
610
FltDisp.LED/LCD
Device
Target on PU
Target on TRIP
Target on PU
Fault Display on LED / LCD
615
Spont. FltDisp.
Device
NO
YES
NO
Spontaneous display of flt.an-
nunciations
625A
T MIN LED HOLD
Device
0 .. 60 min;
∞
0 min
Minimum hold time of lachted
LEDs
640
Start image DD
Device
image 1
image 2
image 3
image 4
image 5
image 6
image 1
Start image Default Display
1103
FullScaleVolt.
P.System Data 2
0.4 .. 1200.0 kV
400.0 kV
Measurement: Full Scale Voltage
(100%)
1104
FullScaleCurr.
P.System Data 2
10 .. 10000 A
1000 A
Measurement: Full Scale Current
(100%)
1105
Line Angle
P.System Data 2
10 .. 89 °
85 °
Line Angle
1106
OPERATION POWER
P.System Data 2
0.2 .. 5000.0 MVA
692.8 MVA
Operational power of protection
zone
1107
P,Q sign
P.System Data 2
not reversed
reversed
not reversed
P,Q operational measured values
sign
1111
x'
P.System Data 2
1A
0.0050 .. 9.5000
Ω
/km
0.1500
Ω
/km
x' - Line Reactance per length
unit
5A
0.0010 .. 1.9000
Ω
/km
0.0300
Ω
/km
1111
x'
P.System Data 2
1A
0.0050 .. 15.0000
Ω
/mi
0.2420
Ω
/mi
x' - Line Reactance per length
unit
5A
0.0010 .. 3.0000
Ω
/mi
0.0484
Ω
/mi
1112
c'
P.System Data 2
1A
0.000 .. 100.000 µF/km
0.010 µF/km
c' - capacit. per unit line len.
µF/km
5A
0.000 .. 500.000 µF/km
0.050 µF/km
1112
c'
P.System Data 2
1A
0.000 .. 160.000 µF/mi
0.016 µF/mi
c' - capacit. per unit line len.
µF/mile
5A
0.000 .. 800.000 µF/mi
0.080 µF/mi
1113
Line Length
P.System Data 2
0.1 .. 1000.0 km
100.0 km
Line Length
1113
Line Length
P.System Data 2
0.1 .. 650.0 Miles
62.1 Miles
Line Length
1114
Tot.Line Length
P.System Data 2
0.1 .. 1000.0 km
100.0 km
Total Line Length
1114
Tot.Line Length
P.System Data 2
0.1 .. 650.0 Miles
62.1 Miles
Total Line Length
1116
RE/RL(Z1)
P.System Data 2
-0.33 .. 10.00
1.00
Zero seq. comp. factor RE/RL for
Z1
1117
XE/XL(Z1)
P.System Data 2
-0.33 .. 10.00
1.00
Zero seq. comp. factor XE/XL for
Z1
1118
RE/RL(> Z1)
P.System Data 2
-0.33 .. 10.00
1.00
Zero seq. comp.factor RE/RL(>
Z1)
1119
XE/XL(> Z1)
P.System Data 2
-0.33 .. 10.00
1.00
Zero seq. comp.factor XE/XL(>
Z1)
1120
K0 (Z1)
P.System Data 2
0.000 .. 4.000
1.000
Zero seq. comp. factor K0 for
zone Z1
1121
Angle K0(Z1)
P.System Data 2
-180.00 .. 180.00 °
0.00 °
Zero seq. comp. angle for zone
Z1
1122
K0 (> Z1)
P.System Data 2
0.000 .. 4.000
1.000
Zero seq.comp.factor K0,higher
zones >Z1
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...