Functions
2.5 Distance Protection
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
162
1641
Op. mode Z5
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode Z5
1642
R(Z5) Ø-Ø
1A
0.050 .. 600.000
Ω
12.000
Ω
R(Z5), Resistance for ph-
ph-faults
5A
0.010 .. 120.000
Ω
2.400
Ω
1643
X(Z5)+
1A
0.050 .. 600.000
Ω
12.000
Ω
X(Z5)+, Reactance for
Forward direction
5A
0.010 .. 120.000
Ω
2.400
Ω
1644
RE(Z5) Ø-E
1A
0.050 .. 600.000
Ω
12.000
Ω
RE(Z5), Resistance for ph-
e faults
5A
0.010 .. 120.000
Ω
2.400
Ω
1645
T5 DELAY
0.00 .. 30.00 sec;
∞
0.90 sec
T5 delay
1646
X(Z5)-
1A
0.050 .. 600.000
Ω
4.000
Ω
X(Z5)-, Reactance for
Reverse direction
5A
0.010 .. 120.000
Ω
0.800
Ω
1651
Op. mode Z1B
Forward
Reverse
Non-Directional
Inactive
Forward
Operating mode Z1B
(overrreach zone)
1652
R(Z1B) Ø-Ø
1A
0.050 .. 600.000
Ω
1.500
Ω
R(Z1B), Resistance for ph-
ph-faults
5A
0.010 .. 120.000
Ω
0.300
Ω
1653
X(Z1B)
1A
0.050 .. 600.000
Ω
3.000
Ω
X(Z1B), Reactance
5A
0.010 .. 120.000
Ω
0.600
Ω
1654
RE(Z1B) Ø-E
1A
0.050 .. 600.000
Ω
3.000
Ω
RE(Z1B), Resistance for
ph-e faults
5A
0.010 .. 120.000
Ω
0.600
Ω
1655
T1B-1phase
0.00 .. 30.00 sec;
∞
0.00 sec
T1B-1phase, delay for
single ph. faults
1656
T1B-multi-phase
0.00 .. 30.00 sec;
∞
0.00 sec
T1B-multi-ph, delay for
multi ph. faults
1657
1st AR -> Z1B
NO
YES
NO
Z1B enabled before 1st
AR (int. or ext.)
1661
Op. mode Z6
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode Z6
1662
R(Z6) Ø-Ø
1A
0.050 .. 600.000
Ω
15.000
Ω
R(Z6), Resistance for ph-
ph-faults
5A
0.010 .. 120.000
Ω
3.000
Ω
1663
X(Z6)+
1A
0.050 .. 600.000
Ω
15.000
Ω
X(Z6)+, Reactance for
Forward direction
5A
0.010 .. 120.000
Ω
3.000
Ω
1664
RE(Z6) Ø-E
1A
0.050 .. 600.000
Ω
15.000
Ω
RE(Z6), Resistance for ph-
e faults
5A
0.010 .. 120.000
Ω
3.000
Ω
1665
T6 DELAY
0.00 .. 30.00 sec;
∞
1.50 sec
T6 delay
1666
X(Z6)-
1A
0.050 .. 600.000
Ω
4.000
Ω
X(Z6)-, Reactance for
Reverse direction
5A
0.010 .. 120.000
Ω
0.800
Ω
Addr.
Parameter
C
Setting Options
Default Setting
Comments
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...