Functions
2.26 Additional Functions
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
485
2.26.11 Energy
Metered values for active and reactive power are determined in the background by the processor system. They
can be called up at the front of the device, read out via the operating interface using a PC with DIGSI, or trans-
ferred to a central master station via the system interface.
2.26.11.1Energy Metering
7SD5 integrates the calculated power which is then made available with the measured values. The compo-
nents as listed in table 2-24 can be read out. The signs of the operating values depend on the setting at address
1107
P,Q sign
(see Section 2.26.4 under margin heading „Display of Measured Values“).
It is important to remember that 7SD5 is, above all, a protection device. The accuracy of the metered values
depends on the instrument transformers (normally protection core) and the device tolerances. The metering is
therefore not suited for tariff purposes.
The counters can be reset to zero or any initial value (see also SIPROTEC 4 System Description).
Table 2-24
Operational metered values
2.26.11.2Setting Notes
Retrieving parameters
The SIPROTEC System Description describes in detail how to read out the statistical counters via the device
front panel or DIGSI. The values are added up in direction of the protected object, provided the direction was
set as „forward“ (address
201
).
2.26.11.3Information List
Measured values
Primary
W
p
+
Active power, output
kWh, MWh, GWh
W
p
–
Active power, input
kWh, MWh, GWh
W
q
+
Reactive power, output
kVARh, MVARh, GVARh
W
q
–
Reactive power, input
kVARh, MVARh, GVARh
No.
Information
Type of In-
formation
Comments
-
Meter res
IntSP_Ev
Reset meter
888
Wp(puls)
PMV
Pulsed Energy Wp (active)
889
Wq(puls)
PMV
Pulsed Energy Wq (reactive)
916
Wp
Δ
=
-
Increment of active energy
917
Wq
Δ
=
-
Increment of reactive energy
924
Wp+=
MVMV
Wp Forward
925
Wq+=
MVMV
Wq Forward
928
Wp-=
MVMV
Wp Reverse
929
Wq-=
MVMV
Wq Reverse
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...