Technical Data
4.1 General
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
575
4.1.4
Communications Interfaces
Protection data interfaces
Operator Interface
Service/modem interface (optional)
See Section 4.2 „Protection Data Interfaces and Communication Topology“
Connection
Front side, non-isolated, RS232,
9-pin D-subminiature female connector for connection of a PC
Operation
With DIGSI
Transmission rate
Min. 4800 Baud; max. 115200 Baud;
Factory Setting: 38400 Baud; Parity: 8E1
Transmission distance
15 m / 50 feet
RS232/RS485/FO
Acc. to ordered variant
Isolated interface for
data transfer
Operation
with DIGSI
RS232/RS485
RS232/RS485 according to the ordering
variant
Connection for panel flush-mounting
housing
Rear panel, mounting location „C“,
9-pole D-subminiature female connector
Shielded data cable
Connection for panel surface-mounting
housing
Shielded data cable
Up to release .../BB At the two-tier terminal
on the case bottom
Release ../CC and higher In the console housing
on the case bottom;
9-pole D-subminiature female connector
Test voltage
500 V; 50 Hz
transmission rate
Min. 4800 Baud; max. 115200 Baud
Factory setting 38400 Baud
RS232
Transmission distance
15 m (50 ft.)
RS485
Transmission distance
1.000 m. (3280 ft.)
Fibre optic cable (FO)
FO connector type
ST connector
Connection for panel flush-mounting
housing
Rear panel, slot „C“
Connection for panel surface-mounting
housing
In console housing at device bottom
Optical wavelength
λ
= 820 nm
Laser class 1 according to EN 60825-1/-2 when using glass fiber 50
μ
m / 125 µm or
when using glass fibre 62.5
μ
m / 125 µm
Permissible optical signal attenuation
max. 8 dB, with glass fibre 62.5
μ
m / 125 µm
Transmission distance
Max. 1.5 km (0.93 miles)
Character idle state
Selectable, factory setting „Light off“
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...