Figure 2-3
Busbar voltage measured via transformer
• Connection of the U
4
input to any other voltage U
X
, which can be processed by the overvoltage protection
function:
Address
210
is then set to:
U4 transformer
=
Ux transformer
.
• If the input U
4
is not required, set:
Address
210
U4 transformer
=
Not connected
.
Factor
Uph / Udelta
(address
211
, see above) is also of importance in this case, as it is used for scaling
the measured data and fault recording data.
Current Connection
The device features four current measurement inputs, three of which are connected to the set of current trans-
formers. Various possibilities exist for the fourth current input
I
4
:
• Connection of the
I
4
input to the earth current in the starpoint of the set of current transformers on the pro-
tected feeder (normal connection):
Address
220
is then set to:
I4 transformer
=
In prot. line
and address
221
I4/Iph CT
=
1
.
• Connection of the
I
4
input to a separate earth current transformer on the protected feeder (e.g. a summation
CT or core balance CT):
Address
220
is then set to:
I4 transformer
=
In prot. line
and address
221
I4/Iph CT
is set:
This is independent of whether the device has a normal measuring current input for
I
4
or a sensitive mea-
suring current input (if necessary with
I
E
transformer for earth fault protection).
All current transformers in the device must be set to the same secondary current (Jumpers).
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...