Mounting and Commissioning
3.3 Commissioning
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
557
Measuring the differential and restraint currents
The test for two ends is terminated with the reading of the differential, restraint and load currents. It is simulta-
neously checked that the current transformer connections have been correctly restored after the
I
4
test (if per-
formed).
• Read out the differential, restraint and load currents. They are available for every phase on the device
display or in DIGSI in the measured values.
– The differential currents must be low, at least one scale less than the currents flowing through. If high
charging currents are to be expected in long overhead lines or cables, these are additionally included in
the differential currents.
– The maximum values of the read measured values for the charging current (3 values) are converted to
Ampere and entered in
I-DIFF>
. The recommended setting for the pickup threshold is 1 ·
I
cN
.
– The restraint currents result from the pickup value
I-DIFF>
(address
1210
, see Section 2.3.2) plus the
sum of the fault currents to be tolerated: Such as the locally permissible current transformer errors ac-
cording to address
253
E% ALF/ALF_N
(see Section 2.1.2), the permissible current transformer errors
at the other ends according to the respective setting, as well as the internal estimation of the system
errors (frequency, synchronisation and delay time difference errors). With the default values for
I-DIFF>
(0.3
I
N
) and
E% ALF/ALF_N
(5.0 % = 0.05) the following ensues:
With
I
the actually flowing current,
I
NB
the rated operational current (as parameterised),
I
N1
the primary nominal current of the local current transformers,
I
N2
the primary nominal current of the current transformers of the remote end.
In the „WEB-Monitor“ the differential and restraint currents are graphically displayed in a characteristics dia-
gram. An example is shown in Figure 3-36.
• If there is a differential current in the size of twice the through-flowing current, you may assume a polarity
reversal of the current transformer(s) at one line end. Again check the polarity and set it right after short-
circuiting all the three current transformers. If you have modified these current transformers, also perform a
power or angle test.
• Finally, open the circuit breaker again.
• If parameter settings have been changed for the tests, reset them to the values necessary for operation.
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...