Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
518
Please note the following:
• The interface modules can only be replaced in devices in flush mounting housing. Interface modules of
devices with surface mounting housing can only be replaced in our manufacturing centre.
• Use only interface modules that can be ordered ex-factory via the ordering code (see also Appendix, Section
• You may have to ensure the termination of the interfaces featuring bus capability according to the margin
heading „RS485 Interface“.
Table 3-17
Exchangeable interface modules
The order numbers of the exchange modules can be found in the Appendix in Section A.1, Accessories.
RS232 interface
Interface RS232 can be modified to interface RS485 and vice versa (see Figures 3-11 and 3-12).
Figure 3-11 shows the location of the jumpers of the RS232 interface on the interface module.
Surface-mounted devices with fibre optics connection have their fibre optics module fitted in the console
housing on the case bottom. The fibre optics module is controlled via an RS232 interface module at the asso-
ciated CPU interface slot. For this application type the jumpers X12 and X13 on the RS232 module are plugged
in position 2-3.
Figure 3-11
Location of the jumpers for configuration of RS232
Terminating resistors are not required for RS232. They are disconnected.
Interface
Mounting Location / Port
Exchange Module
System interface
B
Only interface modules which can be
ordered according to the ordering code
(see also Appendix, Section A.1).
Service interface
C
RS232
RS485
FO 820 nm
Protection data interface 1
D
FO5, FO6; FO17 to FO19, FO30
Protection data interface 2
E
FO5, FO6; FO17 to FO19, FO30
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...