Appendix
A.7 Settings
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
699
3437
ADT SynRequest
Auto Reclose
YES
NO
NO
Request for synchro-check after
3pole AR
3438
T U-stable
Auto Reclose
0.10 .. 30.00 sec
0.10 sec
Supervision time for dead/live
voltage
3440
U-live>
Auto Reclose
30 .. 90 V
48 V
Voltage threshold for live line or
bus
3441
U-dead<
Auto Reclose
2 .. 70 V
30 V
Voltage threshold for dead line or
bus
3450
1.AR: START
Auto Reclose
YES
NO
YES
Start of AR allowed in this cycle
3451
1.AR: T-ACTION
Auto Reclose
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3453
1.AR Tdead 1Flt
Auto Reclose
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
3454
1.AR Tdead 2Flt
Auto Reclose
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3455
1.AR Tdead 3Flt
Auto Reclose
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3456
1.AR Tdead1Trip
Auto Reclose
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1pole trip
3457
1.AR Tdead3Trip
Auto Reclose
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3458
1.AR: Tdead EV.
Auto Reclose
0.01 .. 1800.00 sec
1.20 sec
Dead time after evolving fault
3459
1.AR: CB? CLOSE
Auto Reclose
YES
NO
NO
CB ready interrogation before re-
closing
3460
1.AR SynRequest
Auto Reclose
YES
NO
NO
Request for synchro-check after
3pole AR
3461
2.AR: START
Auto Reclose
YES
NO
NO
AR start allowed in this cycle
3462
2.AR: T-ACTION
Auto Reclose
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3464
2.AR Tdead 1Flt
Auto Reclose
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
3465
2.AR Tdead 2Flt
Auto Reclose
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3466
2.AR Tdead 3Flt
Auto Reclose
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3467
2.AR Tdead1Trip
Auto Reclose
0.01 .. 1800.00 sec;
∞
∞
sec
Dead time after 1pole trip
3468
2.AR Tdead3Trip
Auto Reclose
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3469
2.AR: Tdead EV.
Auto Reclose
0.01 .. 1800.00 sec
1.20 sec
Dead time after evolving fault
3470
2.AR: CB? CLOSE
Auto Reclose
YES
NO
NO
CB ready interrogation before re-
closing
3471
2.AR SynRequest
Auto Reclose
YES
NO
NO
Request for synchro-check after
3pole AR
3472
3.AR: START
Auto Reclose
YES
NO
NO
AR start allowed in this cycle
3473
3.AR: T-ACTION
Auto Reclose
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3475
3.AR Tdead 1Flt
Auto Reclose
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
3476
3.AR Tdead 2Flt
Auto Reclose
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3477
3.AR Tdead 3Flt
Auto Reclose
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3478
3.AR Tdead1Trip
Auto Reclose
0.01 .. 1800.00 sec;
∞
∞
sec
Dead time after 1pole trip
3479
3.AR Tdead3Trip
Auto Reclose
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3480
3.AR: Tdead EV.
Auto Reclose
0.01 .. 1800.00 sec
1.20 sec
Dead time after evolving fault
3481
3.AR: CB? CLOSE
Auto Reclose
YES
NO
NO
CB ready interrogation before re-
closing
3482
3.AR SynRequest
Auto Reclose
YES
NO
NO
Request for synchro-check after
3pole AR
3483
4.AR: START
Auto Reclose
YES
NO
NO
AR start allowed in this cycle
3484
4.AR: T-ACTION
Auto Reclose
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3486
4.AR Tdead 1Flt
Auto Reclose
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
3487
4.AR Tdead 2Flt
Auto Reclose
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3488
4.AR Tdead 3Flt
Auto Reclose
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3489
4.AR Tdead1Trip
Auto Reclose
0.01 .. 1800.00 sec;
∞
∞
sec
Dead time after 1pole trip
3490
4.AR Tdead3Trip
Auto Reclose
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3491
4.AR: Tdead EV.
Auto Reclose
0.01 .. 1800.00 sec
1.20 sec
Dead time after evolving fault
3492
4.AR: CB? CLOSE
Auto Reclose
YES
NO
NO
CB ready interrogation before re-
closing
3493
4.AR SynRequest
Auto Reclose
YES
NO
NO
Request for synchro-check after
3pole AR
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...