Technical Data
4.6 Distance Protection (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
593
Pickup (optional)
Overcurrent Pickup
Overcurrent
I
ph>> for
I
N
= 1 A
0.25 A to 10.00 A
Increments 0.01 A
for
I
N
= 5 A
1.25 A to 50.00 A
Dropout to pickup ratio
Approx. 0.95
Measuring tolerances for sinusoidal measured values
±
5 %
Voltage and angle-dependent current pickup (U/
I
/
ϕ
) (selectable)
Characteristic
Different stages with settable inclinations
Minimum current
I
ph> for
I
N
= 1 A
0.10 A to 4.00 A
Increments 0.01 A
for
I
N
= 5 A
0.50 A to 20.00 A
Current in fault angle range
I
ϕ
for
I
N
= 1 A
0.10 A to 8.00 A
Increments 0.01 A
for
I
N
= 5 A
0.50 A to 40.00 A
Undervoltage phase-earth Uphe
(segregated for
I
ph>,
I
ϕ
> and
I
ph>>)
20 V to 70 V
Increments 1 V
Undervoltage phase-phase Uphph
(segregated for
I
ph>,
I
ϕ
> and
I
ph>>)
40 V to 130 V
Increments 1 V
Lower threshold angle
ϕ
>
30° to 60°
In increments of 1°
Upper threshold angle
ϕ
<
90° to 120°
In increments of 1°
Dropout to pickup ratio
I
ph>,
I
f>
Approx. 0.95
Uphe, Uphph
Approx. 1.05
Measuring tolerances for sinusoidal measured values
Values of U,
I
±
5 %
Angle
ϕ
±
3°
Impedance starting (selectable)
Minimum current
I
ph>
for
I
N
= 1 A
0.05 A to 4.00 A
Increments 0.01 A
for
I
N
= 5 A
0.25 A to 20.00 A
The thresholds of the zone set to the highest level are relevant taking into consideration the corresponding direction
Dropout/pickup ratio
Approx. 1.05
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...