Earth Impedance (Residual) Compensation with Scalar Factors R
E
/R
L
and X
E
/X
L
When entering the resistance ratio R
E
/R
L
and the reactance ratio X
E
/X
L
the addresses
1116
to
1119
apply.
They are calculated separately, and do not correspond to the real and imaginary components of Z
E
/Z
L
. A com-
putation with complex numbers is therefore not necessary! The ratios are obtained from system data using the
following formulas:
Where
R
0
= Zero sequence resistance of the line
X
0
= Zero sequence reactance of the line
R
1
= Positive sequence resistance of the line
X
1
= Positive sequence reactance of the line
These values can be applied either to the entire line or as per unit of length values since the quotients are in-
dependent of length. Furthermore, it makes no difference whether the quotients are calculated with primary, or
secondary values.
Calculation Example:
110 kV overhead line 150 mm
2
with the data
R
1
/s =
0.19
Ω
/km positive sequence impedance
X
1
/s =
0.42
Ω
/km positive sequence impedance
R
0
/s =
0.53
Ω
/km zero sequence impedance
X
0
/s =
1.19
Ω
/km zero sequence impedance
(where s
= line length)
For earth impedance ratios, the following emerge:
The earth impedance (residual) compensation factor setting for the first zone Z1 may be different from that of
the remaining zones of the distance protection. This allows the setting of the exact values for the protected line,
while at the same time the setting for the back-up zones may be a close approximation even when the following
lines have substantially different earth impedance ratios (e.g. cable after an overhead line). Accordingly, the
settings for the address
1116
RE/RL(Z1)
and
1117
XE/XL(Z1)
are determined with the data of the protected
line, while the addresses
1118
RE/RL(> Z1)
and
1119
XE/XL(> Z1)
apply to the remaining zones Z1B and
Z2 up to Z6 (as seen from the relay location).
Resistance ratio:
Reactance ratio:
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...