Technical Data
4.14 Instantaneous High-Current Switch-onto-Fault Protection (SOTF)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
612
4.14
Instantaneous High-Current Switch-onto-Fault Protection (SOTF)
Pickup
Times
High current pickup I>>>
for
I
N
= 1 A
0.10 A to 15.00 A
or
∞
(disabled)
Increments 0.01 A
for
I
N
= 5 A
0.50 A to 75.00 A
or
∞
(disabled)
High current pickup I>>>>
for
I
N
= 1 A
1.00 A to 25.00 A
or
∞
(disabled)
Increments 0.01 A
for
I
N
= 5 A
5.00 A to 125.00 A
or
∞
(disabled)
Dropout to pickup ratio
Approx. 90 %
Pickup tolerance
3 % of setting value or 1 % of
I
N
Shortest trip time
(fast relays/high-speed relays)
Approx. 10 ms / 5 ms
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...