Functions
2.24 Monitoring Functions
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
435
2.24.1.6 Setting Notes
General
The sensitivity of the measured value monitoring can be changed. Experiential values set ex works are ade-
quate in most cases. If particularly high operational asymmetries of the currents and/or voltages are expected,
or if one or more monitoring functions pick up sporadically during normal operation, the sensitivity settings
should be made less sensitve..
The measurement supervision can be switched
ON
or
OFF
in address
2901
MEASURE. SUPERV
.
Symmetry monitoring
Address
2902
BALANCE U-LIMIT
determines the limit voltage (phase-to-phase), above which the voltage
symmetry monitoring is effective. Address
2903
BAL. FACTOR U
is the associated balance factor, i.e. the
gradient of the balance characteristic. The indication
„Fail U balance“
(no. 167) can be delayed at address
2908
T BAL. U LIMIT
. These settings can only be changed using DIGSI at
Additional Settings
.
Address
2904
BALANCE I LIMIT
determines the limit current above which the current symmetry monitoring
is effective. Address
2905
BAL. FACTOR I
is the associated balance factor, i.e. the gradient of the balance
characteristic. The indication
„Fail I balance“
(no. 163) can be delayed at address
2909
T BAL. I
LIMIT
. These settings can only be changed using DIGSI at
Additional Settings
.
Sum monitoring
Address
2906
Σ
I THRESHOLD
determines the limit current above which the current sum monitoring is activat-
ed (absolute portion, only relative to
I
N
). The relative portion (relative to the maximum phase current) for acti-
vating the current sum monitoring is set at address
2907
Σ
I FACTOR
. These settings can only be changed
using DIGSI at
Additional Settings
.
Note
Current sum supervision can operate properly only when the ground current of the protected line is connected
to the fourth current measuring input (
I
4
). The
I
4
transformer must have been configured with parameter
I4
transformer
(address
220
) as . Furthermore, the fourth current measuring must be designed as normal
I
4
transformer. With a sensitive transformer type, the current sum supervision is not active.
Broken wire monitoring
The broken wire monitoring is enabled or disabled via the parameter
2931
BROKEN WIRE
. The differential pro-
tection function is only blocked with the setting
ON
. By means of the setting
Alarm only
, a broken wire can
be signalled; the protection functions are not blocked.
In case of a 1-1/2 circuit breaker arrangement, the parameter
208
1-1/2 CB
is to be set to
YES
. Parameter
2935
Δ
I min
indicates the minimum difference for this circuit breaker arrangement by which the current would
decrease in case of a wire break.
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...