Functions
2.14 Instantaneous High-Current Switch-onto-Fault Protection (SOTF)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
291
Figure 2-146
Activation of the I>>>-Stage
I
>>>> stage
The
I
>>>> stage trips regardless of the position of the circuit breakers. Here, the currents are also numerically
filtered and the peak value of the currents is measured from the double setting value onwards. Figure 2-147
shows the logic diagram in the upper part.
Therefore, this stage is used when current grading is possible. This is possible with a small source impedance
and at the same time a high impedance of the protected object (an example can be found in the advice on
setting notes, Section 2.14.2).
The
I
>>>> stage is enabled automatically by the current-step monitoring
dI
/
dt
of the device for a duration of 50
ms. This stage operates separately for each phase.
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...