Appendix
A.7 Settings
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
702
3755
T Uph-e<<
Voltage Prot.
0.00 .. 100.00 sec;
∞
1.00 sec
T Uph-e<< Time Delay
3758
CURR.SUP. Uphe<
Voltage Prot.
ON
OFF
ON
Current supervision (Uph-e)
3759A
Uph-e<(<) RESET
Voltage Prot.
1.01 .. 1.20
1.05
Uph-e<(<) Reset ratio
3761
Uph-ph<(<)
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF
Operating mode Uph-ph under-
voltage prot.
3762
Uph-ph<
Voltage Prot.
1.0 .. 175.0 V; 0
50.0 V
Uph-ph< Pickup
3763
T Uph-ph<
Voltage Prot.
0.00 .. 100.00 sec;
∞
2.00 sec
T Uph-ph< Time Delay
3764
Uph-ph<<
Voltage Prot.
1.0 .. 175.0 V; 0
17.0 V
Uph-ph<< Pickup
3765
T Uphph<<
Voltage Prot.
0.00 .. 100.00 sec;
∞
1.00 sec
T Uph-ph<< Time Delay
3768
CURR.SUP.Uphph<
Voltage Prot.
ON
OFF
ON
Current supervision (Uph-ph)
3769A
Uphph<(<) RESET
Voltage Prot.
1.01 .. 1.20
1.05
Uph-ph<(<) Reset ratio
3771
U1<(<)
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF
Operating mode U1 undervolt-
age prot.
3772
U1<
Voltage Prot.
1.0 .. 100.0 V; 0
30.0 V
U1< Pickup
3773
T U1<
Voltage Prot.
0.00 .. 100.00 sec;
∞
2.00 sec
T U1< Time Delay
3774
U1<<
Voltage Prot.
1.0 .. 100.0 V; 0
10.0 V
U1<< Pickup
3775
T U1<<
Voltage Prot.
0.00 .. 100.00 sec;
∞
1.00 sec
T U1<< Time Delay
3778
CURR.SUP.U1<
Voltage Prot.
ON
OFF
ON
Current supervision (U1)
3779A
U1<(<) RESET
Voltage Prot.
1.01 .. 1.20
1.05
U1<(<) Reset ratio
3802
START
Fault Locator
Pickup
TRIP
Pickup
Start fault locator with
3805
Paral.Line Comp
Fault Locator
NO
YES
YES
Mutual coupling parall.line com-
pensation
3806
Load Compensat.
Fault Locator
NO
YES
NO
Load Compensation
3807
two ended
Fault Locator
ON
OFF
ON
two ended fault location
3811
Tmax OUTPUT BCD
Fault Locator
0.10 .. 180.00 sec
0.30 sec
Maximum output time via BCD
3901
FCT BreakerFail
Breaker Failure
ON
OFF
ON
Breaker Failure Protection
3902
I> BF
Breaker Failure
1A
0.05 .. 20.00 A
0.10 A
Pick-up threshold I>
5A
0.25 .. 100.00 A
0.50 A
3903
1p-RETRIP (T1)
Breaker Failure
NO
YES
YES
1pole retrip with stage T1 (local
trip)
3904
T1-1pole
Breaker Failure
0.00 .. 30.00 sec;
∞
0.00 sec
T1, Delay after 1pole start (local
trip)
3905
T1-3pole
Breaker Failure
0.00 .. 30.00 sec;
∞
0.00 sec
T1, Delay after 3pole start (local
trip)
3906
T2
Breaker Failure
0.00 .. 30.00 sec;
∞
0.15 sec
T2, Delay of 2nd stage (busbar
trip)
3907
T3-BkrDefective
Breaker Failure
0.00 .. 30.00 sec;
∞
0.00 sec
T3, Delay for start with defective
bkr.
3908
Trip BkrDefect.
Breaker Failure
NO
with T1-trip
with T2-trip
w/ T1/T2-trip
NO
Trip output selection with defec-
tive bkr
3909
Chk BRK CONTACT
Breaker Failure
NO
YES
YES
Check Breaker contacts
3912
3I0> BF
Breaker Failure
1A
0.05 .. 20.00 A
0.10 A
Pick-up threshold 3I0>
5A
0.25 .. 100.00 A
0.50 A
3913
T2StartCriteria
Breaker Failure
With exp. of T1
Parallel withT1
Parallel withT1
T2 Start Criteria
3921
End Flt. stage
Breaker Failure
ON
OFF
OFF
End fault protection
3922
T-EndFault
Breaker Failure
0.00 .. 30.00 sec;
∞
2.00 sec
Trip delay of end fault protection
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...