Functions
2.1 General
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
68
2.1.4.2
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding second-
ary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
1103
FullScaleVolt.
0.4 .. 1200.0 kV
400.0 kV
Measurement: Full Scale
Voltage (100%)
1104
FullScaleCurr.
10 .. 10000 A
1000 A
Measurement: Full Scale
Current (100%)
1105
Line Angle
10 .. 89 °
85 °
Line Angle
1106
OPERATION POWER
0.2 .. 5000.0 MVA
692.8 MVA
Operational power of pro-
tection zone
1107
P,Q sign
not reversed
reversed
not reversed
P,Q operational measured
values sign
1111
x'
1A
0.0050 .. 9.5000
Ω
/km
0.1500
Ω
/km
x' - Line Reactance per
length unit
5A
0.0010 .. 1.9000
Ω
/km
0.0300
Ω
/km
1111
x'
1A
0.0050 .. 15.0000
Ω
/mi
0.2420
Ω
/mi
x' - Line Reactance per
length unit
5A
0.0010 .. 3.0000
Ω
/mi
0.0484
Ω
/mi
1112
c'
1A
0.000 .. 100.000 µF/km
0.010 µF/km
c' - capacit. per unit line
len. µF/km
5A
0.000 .. 500.000 µF/km
0.050 µF/km
1112
c'
1A
0.000 .. 160.000 µF/mi
0.016 µF/mi
c' - capacit. per unit line
len. µF/mile
5A
0.000 .. 800.000 µF/mi
0.080 µF/mi
1113
Line Length
0.1 .. 1000.0 km
100.0 km
Line Length
1113
Line Length
0.1 .. 650.0 Miles
62.1 Miles
Line Length
1114
Tot.Line Length
0.1 .. 1000.0 km
100.0 km
Total Line Length
1114
Tot.Line Length
0.1 .. 650.0 Miles
62.1 Miles
Total Line Length
1116
RE/RL(Z1)
-0.33 .. 10.00
1.00
Zero seq. comp. factor
RE/RL for Z1
1117
XE/XL(Z1)
-0.33 .. 10.00
1.00
Zero seq. comp. factor
XE/XL for Z1
1118
RE/RL(> Z1)
-0.33 .. 10.00
1.00
Zero seq. comp.factor
RE/RL(> Z1)
1119
XE/XL(> Z1)
-0.33 .. 10.00
1.00
Zero seq. comp.factor
XE/XL(> Z1)
1120
K0 (Z1)
0.000 .. 4.000
1.000
Zero seq. comp. factor K0
for zone Z1
1121
Angle K0(Z1)
-180.00 .. 180.00 °
0.00 °
Zero seq. comp. angle for
zone Z1
1122
K0 (> Z1)
0.000 .. 4.000
1.000
Zero seq.comp.factor
K0,higher zones >Z1
1123
Angle K0(> Z1)
-180.00 .. 180.00 °
0.00 °
Zero seq. comp. angle,
higher zones >Z1
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...