Functions
2.24 Monitoring Functions
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
442
2.24.2.2 Setting Notes
General
The number of circuits to be supervised was set during the configuration in address
140
Trip Cir. Sup.
(Section 2.1.1.3). If the trip circuit supervision is not used at all, the setting
Disabled
must be applied there.
The trip circuit supervision can be switched
ON
or
OFF
in address
4001
FCT TripSuperv.
. The number of
binary inputs that shall be used in each of the supervised circuits is set in address
4002
No. of BI
. If the
routing of the binary inputs required for this does not comply with the selected supervision mode, an alarm is
given (
„TripC1 ProgFAIL ...“
, with identification of the non-compliant circuit).
Supervision with one binary input
The alarm for supervision with two binary inputs is always delayed by approx. 1 s to 2 s, whereas the delay time
of the alarm for supervision with one binary input can be set in address
4003
Alarm Delay
. 1 s to 2 s are
sufficient if only the 7SD5 device is connected to the trip circuits as the trip circuit supervision does not operate
during a system fault. If, however, trip contacts from other devices are connected in parallel in the trip circuit,
the alarm must be delayed such that the longest trip command duration can be reliably bridged.
2.24.2.3 Settings
2.24.2.4 Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
4001
FCT TripSuperv.
ON
OFF
OFF
TRIP Circuit Supervision is
4002
No. of BI
1 .. 2
2
Number of Binary Inputs per trip
circuit
4003
Alarm Delay
1 .. 30 sec
2 sec
Delay Time for alarm
No.
Information
Type of In-
formation
Comments
6854
>TripC1 TripRel
SP
>Trip circuit superv. 1: Trip Relay
6855
>TripC1 Bkr.Rel
SP
>Trip circuit superv. 1: Breaker Relay
6856
>TripC2 TripRel
SP
>Trip circuit superv. 2: Trip Relay
6857
>TripC2 Bkr.Rel
SP
>Trip circuit superv. 2: Breaker Relay
6858
>TripC3 TripRel
SP
>Trip circuit superv. 3: Trip Relay
6859
>TripC3 Bkr.Rel
SP
>Trip circuit superv. 3: Breaker Relay
6861
TripC OFF
OUT
Trip circuit supervision OFF
6865
FAIL: Trip cir.
OUT
Failure Trip Circuit
6866
TripC1 ProgFAIL
OUT
TripC1 blocked: Binary input is not set
6867
TripC2 ProgFAIL
OUT
TripC2 blocked: Binary input is not set
6868
TripC3 ProgFAIL
OUT
TripC3 blocked: Binary input is not set
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...