Functions
2.8 Earth Fault Protection in Earthed Systems (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
234
2.8.2
Setting Notes
General
During the configuration of the device scope of functions (refer to Section 2.1.1, address
131
Earth Fault
O/C
) it was determined which group of characteristics is to be available. Only those parameters that apply to
the available characteristics, according to the selected configuration and the version of the device, are acces-
sible in the procedures described below.
Parameter
3101
FCT EarthFltO/C
can be used to switch the earth fault protection
ON
or
OFF
. This refers to
all stages of the earth fault protection.
If not required, each of the four stages can be deactivated by setting its
MODE...
to
Inactive
(see below).
Blocking
The earth fault protection can be blocked by the distance protection to give preference to the selective fault
clearance by the distance protection over tripping by the earth fault protection. In address
3102
BLOCK for
Dist.
it is determined whether blocking is performed during each fault detection of the distance protection
(
every PICKUP
) or only during single-phase fault detection by the distance protection (
1phase PICKUP
) or
only during multiple-phase fault detection by the distance protection (
multiph. PICKUP
). If blocking is not
desired, set
NO
.
It is also possible to block the earth fault protection trip only for pickup of the distance protection on the protect-
ed line section. To block the earth fault protection for faults occurring within zone Z1, set address
3174
BLK
for DisZone
to
in zone Z1
. To block the earth fault protection for faults occurring within zone Z1 or Z1B,
set address
3174
BLK for DisZone
to
in zone Z1/Z1B
. If, however, blocking of the earth fault protection
by the distance protection is to take effect regardless of the fault location, set address
3174
BLK for
DisZone
to
in each zone
.
Address
3102
thus refers to the fault type and address
3174
to the fault location. The two blocking options
create an AND condition. To block the earth fault protection only for single-phase faults occurring in zone Z1,
set address
3102
BLOCK for Dist.
=
1phase PICKUP
and
3174
BLK for DisZone
=
in zone Z1
. To
block the earth fault protection for any fault type (any distance protection pickup) occurring within zone Z1, the
setting
3102
BLOCK for Dist.
=
every PICKUP
and
3174
BLK for DisZone
=
in zone Z1
applies.
The earth fault protection must be blocked during single-pole automatic reclose dead time to avoid pickup with
the zero-sequence values and, if applicable, the negative sequence values arising during this state.
When setting the power system data (Section 2.1.2.1), it was specified whether all stages of the earth fault pro-
tection are blocked together or separately during the single-pole dead time.
When setting
238
EarthFltO/C 1p
to
stages together
, parameter
3103
BLOCK 1pDeadTim
becomes
visible; the parameters for phase-selective blocking are hidden.
Parameter
3103
BLOCK 1pDeadTim
must be set to
YES
(presetting for devices with single-pole tripping) if a
single-pole automatic reclosure is to be performed. If not, set
NO
.
Setting parameter
3103
BLOCK 1pDeadTim
to
YES
completely blocks the earth fault protection if the Open
Pole Detector has recognized a single-pole dead time. If no single-pole tripping is carried out in the protected
network, this parameter should be set to
NO
.
Regardless of how parameter address
3103
BLOCK 1pDeadTim
is set, the earth fault protection will always
be blocked during the single-pole dead time, if it has issued a trip command itself. This is necessary because
otherwise the picked up earth fault protection cannot drop out if the fault current was caused by load current.
When setting
stages separat.
, the parameters for phase-selective blocking become visible (
3116
BLK
/1p 3I0>>>
,
3126
BLK /1p 3I0>>
,
3136
BLK /1p 3I0>
and
3157
BLK /1p 3I0p
), parameter
3103
BLOCK 1pDeadTim
is hidden.
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...