Functions
2.10 Restricted Earth Fault Protection (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
269
It was assumed in the above examples that the currents 3
I
0
" and 3
I
0
' are in counter-phase for external earth
faults which is, is in fact, true for the primary measured quantities. Current transformer saturation may, however,
feign a phase displacement between the starpoint current and the sum of the phase currents which reduces
the restaint quantity. With
ϕ
(3
I
0
"; 3
I
0
') = 90° the restraint quantity is zero. This corresponds to the conventional
direction determination using the method of summation and and difference comparison.
Figure 2-136
Phasor diagram of the restraint quantity during external fault
The restraint quantity can be influenced by a factor k. This factor has a certain relationship to the limit angle
ϕ
limit
.
This limit angle determines for which phase displacement between 3
I
0
" and 3
I
0
' the pickup value for 3
I
0
" = 3
I
0
'
grows to
∞
, i.e. no pickup occurs. In 7SD5 k = 4.
In the aforementioned example 1), the restraint quantity
I
Rest
is quadrupled once more; thus, it becomes 8 times
the tripping quantity
I
REF
.
The threshold angle
ϕ
Limit
= 100°. That means no trip is possible for phase displacement
ϕ
(3
I
0
"; 3
I
0
')
≥
100°.
Figure 2-137 shows the operating characteristics of the restricted earth fault protection dependent of the phase
displacement between 3
I
0
" and 3
I
0
' for a constant infeed ratio |3
I
0
"| = |3
I
0
'|.
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...