Appendix
A.7 Settings
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
697
3151
IEC Curve
Earth Fault O/C
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse
IEC Curve
3152
ANSI Curve
Earth Fault O/C
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse
ANSI Curve
3153
LOG Curve
Earth Fault O/C
Log. inverse
Log. inverse
LOGARITHMIC Curve
3154
3I0p Startpoint
Earth Fault O/C
1.0 .. 4.0
1.1
Start point of inverse characteris-
tic
3155
k
Earth Fault O/C
0.00 .. 3.00 sec
0.50 sec
k-factor for Sr-characteristic
3156
S ref
Earth Fault O/C
1A
1 .. 100 VA
10 VA
S ref for Sr-characteristic
5A
5 .. 500 VA
50 VA
3157
BLK /1p 3I0p
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
YES
No (non-dir.)
YES
Block 3I0p during 1pole dead
time
3158
Trip 1p 3I0p
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
YES
NO
YES
Single pole trip with 3I0p
3160
POLARIZATION
Earth Fault O/C
U0 + IY or U2
U0 + IY
with IY only
with U2 and I2
zero seq. power
U0 + IY or U2
Polarization
3162A
Dir. ALPHA
Earth Fault O/C
0 .. 360 °
338 °
ALPHA, lower angle for forward
direction
3163A
Dir. BETA
Earth Fault O/C
0 .. 360 °
122 °
BETA, upper angle for forward di-
rection
3164
3U0>
Earth Fault O/C
0.5 .. 10.0 V
0.5 V
Min. zero seq.voltage 3U0 for po-
larizing
3165
IY>
Earth Fault O/C
1A
0.05 .. 1.00 A
0.05 A
Min. earth current IY for polariz-
ing
5A
0.25 .. 5.00 A
0.25 A
3166
3U2>
Earth Fault O/C
0.5 .. 10.0 V
0.5 V
Min. neg. seq. polarizing voltage
3U2
3167
3I2>
Earth Fault O/C
1A
0.05 .. 1.00 A
0.05 A
Min. neg. seq. polarizing current
3I2
5A
0.25 .. 5.00 A
0.25 A
3168
PHI comp
Earth Fault O/C
0 .. 360 °
255 °
Compensation angle PHI comp.
for Sr
3169
S forward
Earth Fault O/C
1A
0.1 .. 10.0 VA
0.3 VA
Forward direction power thresh-
old
5A
0.5 .. 50.0 VA
1.5 VA
3170
2nd InrushRest
Earth Fault O/C
10 .. 45 %
15 %
2nd harmonic ratio for inrush re-
straint
3171
Imax InrushRest
Earth Fault O/C
1A
0.50 .. 25.00 A
7.50 A
Max.Current, overriding inrush
restraint
5A
2.50 .. 125.00 A
37.50 A
3172
SOTF Op. Mode
Earth Fault O/C
PICKUP
DIRECT.
DIRECT.
Instantaneous mode after
SwitchOnToFault
3173
SOTF Time DELAY
Earth Fault O/C
0.00 .. 30.00 sec
0.00 sec
Trip time delay after SOTF
3174
BLK for DisZone
Earth Fault O/C
in zone Z1
in zone Z1/Z1B
in each zone
in each zone
Block E/F for Distance Protection
Pickup
3175
EF BLK Dif.PU
Earth Fault O/C
YES
NO
YES
Block E/F for Differential Prot.
Pickup
3182
3U0>(U0 inv)
Earth Fault O/C
1.0 .. 10.0 V
5.0 V
3U0> setpoint
3183
U0inv. minimum
Earth Fault O/C
0.1 .. 5.0 V
0.2 V
Minimum voltage U0min for T-
>oo
3184
T forw. (U0inv)
Earth Fault O/C
0.00 .. 32.00 sec
0.90 sec
T-forward Time delay (U0inv)
3185
T rev. (U0inv)
Earth Fault O/C
0.00 .. 32.00 sec
1.20 sec
T-reverse Time delay (U0inv)
3186A
3U0< forward
Earth Fault O/C
0.1 .. 10.0 V; 0
0.0 V
3U0 min for forward direction
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...