Technical Data
4.6 Distance Protection (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
594
Distance measurement
Characteristic
Polygonal or MHO characteristic (depending on ordered vari-
ant); 6 independent zones and 1 controlled zone
Setting ranges of polygon:
I
Ph
> = min. current phases
for
I
N
= 1 A
0.05 A to 4.00 A
Increments 0.01 A
for
I
N
= 5 A
0.25 A to 20.00 A
X = reactance reach
for
I
N
= 1 A
0.050
Ω
to 600,000
Ω
Increments 0.001
Ω
for
I
N
= 5 A
0.010
Ω
to 120,000
Ω
R = resistance tolerance phase-phase
for
I
N
= 1 A
0.050
Ω
to 600,000
Ω
Increments 0.001
Ω
for
I
N
= 5 A
0.010
Ω
to 120,000
Ω
RE = resistance tolerance phase-earth
for
I
N
= 1 A
0.050
Ω
to 600,000
Ω
Increments 0.001
Ω
for
I
N
= 5 A
0.010
Ω
to 120,000
Ω
ϕ
Line
= line angle
10° to 89°
Increments 1°
ϕ
Dist
= angle of distance protection characteristic
30° to 90°
Increments 1°
α
Pol
= tilt angle for 1st zone
0° to 30°
Increments 1°
Direction determination for polygonal characteristic:
For all types of faults
With phase-true, memorized or cross-polarized voltages
Directional sensitivity
Dynamically unlimited
Stationary approx. 1V
Each zone can be set to operate in forward or reverse direction, non-directional or ineffective.
Setting ranges of the MHO characteristic:
I
PH
> = min. current, phases
for
I
N
= 1 A
0.05 A to 4.00 A
Increments 0.01 A
for
I
N
= 5 A
0.25 A to 20.00 A
Z
r
= impedance reach
for
I
N
= 1 A
0.050
Ω
to 200,000
Ω
Increments 0.001
Ω
for
I
N
= 5 A
0.010
Ω
to 40,000
Ω
ϕ
Line
= line angle
10° to 89°
Increments 1°
ϕ
Dist
= angle of distance protection characteristic
30° to 90°
Increments 1°
Polarization
With memorized or cross-polarized voltages
Each zone can be set to operate in forward or reverse direction or ineffective.
Load trapezoid:
R
Load
= minimum load resistance
for
I
N
= 1 A
0.050
Ω
to 600,000
Ω
;
∞
Increments 0.001
Ω
for
I
N
= 5 A
0.010
Ω
to 120,000
Ω
;
∞
ϕ
Load
= maximum load angle
20° to 60°
Increments 1°
Dropout ratio
– Currents
Approx. 0.95
– Impedances
Approx. 1.06
Measured value correction
Mutual impedance matching for parallel lines (order option)
Measuring tolerances for sinusoidal measured values
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...