Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
516
Table 3-13
Jumper setting for
Nominal Current
or
Measuring Range
1)
Not for variant with sensitive earth fault detection
Contacts of relays for binary outputs BO13, BO14 and BO15 can be configured as normally open or normally
closed contacts (see also General Diagrams in the Appendix).
Table 3-14
Jumper setting for the
contact type
of the relay for BO13, BO14 and BO15
1)
As-supplied state
The relays for the binary outputs BO8 to BO12 can be connected to common potential, or configured individu-
ally for BO8, BO11 and BO12 (BO9 and BO10 are without function in this context) (see also General Diagrams
in the Appendix).
Table 3-15
Jumper settings for the configuration of the
common potential
from BO8 to BO11 or for the
setting of BO8, BO11 and BO12 as
single relays
1)
As-supplied state
Jumpers X71, X72 and X73 serve for setting the bus address. Their position must not be changed. The follow-
ing table shows the preset jumper positions.
Table 3-16
Jumper setting of the
module addresses
of the input/output board C-I/O-2
Jumper
Nominal current 1 A
Measuring range 20 A
Nominal current 5 A
Measuring range 100 A
X51
1-2
1-2
X60
1-2
2-3
X61
2-5
3-5
X62
2-5
3-5
X63
2-5
3-5
X64
2-5
3-5
For
Jumper
Open in quiescent state (NO)
Closed in quiescent state (NC)
BO13
X41
1-2
2-3
BO14
X42
1-2
2-3
BO15
X43
1-2
2-3
Jumper
BO8 to BO12 connected to common
potential
BO8, BO11, BO12 configured as single relays
(BO9, BO10 without function)
X80
1-2, 3-4
2-3, 4-5
X81
1-2, 3-4
2-3, 4-5
X82
2-3
1-2
Jumper
Factory setting
X71
1-2 (H)
X72
1-2 (H)
X73
2-3 (L)
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...