Euro Stopper
®
- STI-15000 Series
The Euro Stopper is a sleek protective cover that offers protection
against tampering, vandalism and damage from accidental activation.
Specifications
• Input power 3V Lithium CR123A, 12-24 VDC, remote power
• Flammability: UL94 V-2
• Temperature range:
· Polycarbonate Rated: -40° to 121°C (-40° to 250°F)
· Electronics Operating Range: -10° to 49°C (14 to 120° F)
Mounting Instructions
1.
Position the Euro Stopper over the device to be protected, open the front
cover of the Euro Stopper and mark the position for the four (4) mounting screws
2.
Drill holes and attach the Euro Stopper to the wall using the screws provided.
See Fig. 1 for drill sizes.
3.
If a surface spacer is included, ensure the isolated (screw) mounting columns
are at the top (Fig. 2).
Note: The spacer is not reversible; arrows are marked upwards on the removable
plastic windows for your convenience (Fig. 2).
WHEN USING ANCHORS,
DRILL 3/16 in. (5mm)
DIA. HOLES 1 1/4 in.
(31.75mm) DEEP
IF USING SCREWS ONLY, DRILL
1/8 in. (30mm) DIA. HOLES
1 1/4 in. (32mm) DEEP
EURO STOPPER
ASSEMBLY
SCREWS
(4) PROVIDED
SPACER
RAWL PLUGS
(4) PROVIDED
WINDOW
FOR SPACER
(2) PROVIDED
WINDOW
FOR CONDUIT
(2) PROVIDED
4.
The 32mm (1.25”) and 50mm (2”) surface spacer provides cable entry
facilities for conduit, cable and trunking.
5.
For surface installation, use the window attached to the spacer to fill
in any unused cable/conduit entry points.
MOUNTING COLUMNS
Fig. 1
Fig. 2
86mm (3.40 in.)
TEXT HERE
152mm
(6.00 in.)
Circuit Board Operations
Fig. 3
Alarm Cur
r
ent:
15000 series
0217_12
}
}
SERVICE PIN
(1) PROVIDED
M276 HORN CASE
34080 PCB SOUNDER
#4 x .312 in.
HI-LOW SCREW
(2) PROVIDED
#2 x .25 in. SMS
(2) PROVIDED
M272 HORNSHELL
VOLUME SWITCH
HI/OFF/LO
Fig. 4
Toll Free: 800-888-4784 • E-mail: [email protected]
Web: www.sti-usa.com
USA - Headquarters
2306 Airport Road • Waterford, Michigan 48327-1209
Phone: 248-673-9898 • Fax: 248-673-1246
Tel: 44 (0) 1527 520 999 Fax: 44 (0) 1527 501 999
E-mail: [email protected] • Web: www.sti-emea.com
European Office
Taylor House • 34 Sherwood Road • Bromsgrove
Worcestershire • B60 3DR • England
Toll Free: 800-888-4784 • E-mail: [email protected]
Web: www.sti-usa.com
USA - Headquarters
2306 Airport Road • Waterford, Michigan 48327-1209
Phone: 248-673-9898 • Fax: 248-673-1246
Tel: 44 (0) 1527 520 999 Fax: 44 (0) 1527 501 999
E-mail: [email protected] • Web: www.sti-emea.com
European Office
Taylor House • 34 Sherwood Road • Bromsgrove
Worcestershire • B60 3DR • England
V
olume:
3V B
a
ttery
12V
24V
St
and
by
10µA
500µA
550µA
Low
40mA
38mA
22mA
Hi
g
h
105mA
125mA
95mA
Distance
1m (3
ft
)
3m (10
ft
)
Low
72 dB
64 dB
High
96 dB
88 dB
Wire
Descrip
ti
on
RED
+ REMOTE INPUT
Form “C”
BLACK
POWER 12-24VDC
Dry Contact Relay
BLUE
COMMON
30VDC, 1a
GREEN
NC: NORMALLY CLOSED
125VAC, 0.5A
YELLOW
NO: NORMALLY OPEN
60VDC, 0.3A
-
1.
On initial installation, activate the battery by removing the battery
cover using a small Phillips screwdriver. Remove red tape.
2.
To adjust the volume using the Hi/OFF/Lo switch, remove horn case
(see Fig. 4 for location).
3.
If using 12/24VDC & Relay Cord:
A.
Remove horn case.
B.
Remove PCB by removing the two (2) screws as shown in Fig. 5.
Lift PCB as far as the wires allow.
C.
Drill a 5mm hole (3/16”) at the witness point shown on Fig. 5.
D.
Then insert the wire harness cord into the socket as shown in Fig. 5.
E.
Leaving a small amount of slack, push the harness into the drilled
outlet hole.
F.
Secure PCB into place and reattach horn case with two (2) provided
screws.
G. CAUTION: The relay and sounder will not operate with the
service pin in place.