Functions
2.1 General
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
50
The rated accuracy limit factor n of the current transformers and the rated power P
N
are usually stated on the
rating plate of the current transformers. The information refers to nominal conditions (nominal current, nominal
burden). For example (according to VDE 0414 / Part 1 or IEC 60044)
Current transformer 10P10; 30 VA
→
n = 10; P
N
= 30 VA
Current transformer 10P20; 20 VA
→
n = 20; P
N
= 20 VA
The operational accuracy limit factor n' is derived from these rated data and the actual secondary burden P':
With
n' =
operational accuracy limit factor (effective overcurrent factor)
n =
rated accuracy limit factor of the current transformers (distinctive number behind P)
P
N
=
rated burden of the current transformers [VA] at rated current
P
i
=
internal burden of the current transformers [VA] at rated current
P' =
actually connected burden (d secondary lines) [VA] at rated current
Usually, the internal burden of the current transformers is stated in the test report. If it is unknown, it can be
roughly calculated from the DC resistance R
i
of the secondary winding.
P
i
≈
R
i
·
I
N
2
The ratio between operational accuracy limit factor and rated accuracy limit factor n'/n is set at address
251
K_ALF/K_ALF_N
.
The CT error at rated current, plus a safety margin, is set at address
253
E% ALF/ALF_N
. It is equal to the
„current measuring deviation for primary nominal current intensity F1“ according to VDE 0414 / Part 1 or IEC
60044. It is
– 3 % for a 5P transformer,
– 5 % for a 10P transformer.
The CT error at rated accuracy limit factor, plus a safety margin, is set at address
254
E% K_ALF_N
. It is
derived from the number preceding the P of the transformer data.
Table 2-1 illustrates some usual protective current transformer types with their characteristic data and the rec-
ommended settings.
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...