Functions
2.7 Teleprotection for Distance Protection (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
214
The parameter
Mem.rec.sig.
(address
2113
) is only effective for the schemes
PUTT (Z1B)
with zone ac-
celeration,
POTT
, and
UNBLOCKING
. If the parameter
Mem.rec.sig.
(address
2113
) is set to
YES
and an
own distance protection pickup is available in Z1B, the phase-selective release effected via the teleprotection
scheme is stored. Storing the received signal makes sense if the teleprotection scheme is used in ring net-
works as a backup protection with increased grading time.
Transient blocking
The parameters
TrBlk Wait Time
and
TrBlk BlockTime
serve the transient blocking with the permissive
(overreaching) schemes. With permissive underreach transfer trip schemes they are of no consequence.
The time
TrBlk Wait Time
(address
2109
) is a waiting time prior to transient blocking. The transient blocking
will be activated in the permissive overreach transfer schemes only after the distance protection has not de-
tected a fault in forward direction within this time after fault detection. In the case of the blocking scheme, the
waiting time prevents transient blocking in the event that the blocking signal reception from the opposite line
end is very fast. With the setting
∞
there is no transient blocking. This parameter can only be changed in DIGSI
at
Display Additional Settings
.
Note
With
POTT
and
UNBLOCKING
schemes, the
TrBlk Wait Time
must not be set too short to prevent unwanted
activation of the transient blocking
TrBlk BlockTime
when the direction measurement is delayed compared
to the function pickup (signal transients). A setting of 10 ms to 40 ms is generally applicable depending on the
operating (tripping) time of the relevant circuit breaker on the parallel line.
It is absolutely necessary that the transient blocking time
TrBlk BlockTime
(address
2110
) is longer than
the duration of transients resulting from the inception or clearance of external short circuits. During this time the
send signal is blocked for the permissive overreach schemes
POTT
and
UNBLOCKING
if the protection had ini-
tially detected a reverse fault. In the case of blocking scheme
BLOCKING
, the blocking of the Z1B release is
prolonged by this time by both the detection of a reverse fault and the (blocking) received signal. After expira-
tion of
TrBlk BlockTime
(address
2110
) the delay time
Release Delay
(address
2108
) is restarted for
the blocking scheme. Since the blocking scheme always requires setting the delay time
Release Delay
, the
transient blocking time
TrBlk BlockTime
(address
2110
) can usually be set very short. This parameter can
only be altered with DIGSI under
Additional Settings
.
Where the teleprotection schemes of the distance protection and earth fault protection share the same channel,
DIS TRANSBLK EF
(address
2112
) should be set to
YES
. This blocks also the distance protection if an external
fault was previously detected by the earth fault protection only.
Echo function
The echo function settings are common to all weak infeed measures and summarized in tabular form in Section
2.11.2.2.
Note
The
„ECHO SIGNAL“
(No. 4246) must be allocated separately to the output relays for the transmitter actuation,
as it is not contained in the transmit signals of the transmission functions.
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...