Functions
2.1 General
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
44
2.1.2
General Power System Data (Power System Data 1)
The device requires some plant and power system data in order to be able to adapt its functions accordingly,
depending on the actual application. The data required include for instance rated data of the substation and the
measuring transformers, polarity and connection of the measured quantities, if necessary features of the circuit
breakers, and others. Furthermore, there are several function parameters associated with several functions
rather than one specific protection, control or monitoring function. The Power System Data 1 can only be
changed from a PC running DIGSI and are discussed in this section.
2.1.2.1
Setting Notes
Polarity of the current transformers
In address
201
CT Starpoint
, the polarity of the wye-connected current transformers is specified (the fol-
lowing figure also goes for only two current transformers). The setting determines the measuring direction of
the device (forward = line direction). A change in this setting also results in a polarity reversal of the earth
current inputs
I
E
or
I
EE
.
142
Therm.Overload
Disabled
Enabled
Disabled
Thermal Overload Protection
143
TRANSFORMER
NO
YES
NO
Transformer inside protection
zone
144
V-TRANSFORMER
Not connected
connected
connected
Voltage transformers
145
P. INTERFACE 1
Enabled
Disabled
IEEE C37.94
Enabled
Protection Interface 1 (Port D)
146
P. INTERFACE 2
Disabled
Enabled
IEEE C37.94
Disabled
Protection Interface 2 (Port E)
147
NUMBER OF RELAY
2 relays
3 relays
4 relays
5 relays
6 relays
2 relays
Number of relays
148
GPS-SYNC.
Enabled
Disabled
Disabled
GPS synchronization
149
charge I comp.
Enabled
Disabled
Disabled
charging current compensation
160
L-sections FL
1 Section
2 Sections
3 Sections
1 Section
Line sections for fault locator
Addr.
Parameter
Setting Options
Default Setting
Comments
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...