Configuration
5-39
7SA522 Manual
C53000-G1176-C119-2
The utilized processor capacity which is available for the CFC can be checked under
2SWLRQ
→
5HSRUWV
in the register
&KHFNFRQVLVWHQF\
. By scrolling, an area is
reached, where information regarding the cumulated memory consumption of the
memory reserved for CFC can be read in percent. Figure 5-35 is an example showing
an over-utilization by 56 % in the task level PLC_BEARB (marked in the Figure), while
the other task levels are within the permissible range.
Figure 5-35
Read-out of the CFC configuration degree of utilization
If the limits are exceeded during configuration of the CFC, DIGSI
®
4 issues a warning
(refer to Figure 5-36). After acknowledgement of this alarm, the system utilisation can
be viewed as described above.
Figure 5-36
Warning message on reaching the limits
Table 5-9
Processing times in TICKS required by the individual elements
Individual Element
Amount of TICKS
Module, basic requirement
5
each input more than 3 inputs for generic modules
1
Connection to an input
6
Connection to an output signal
7
Additional for each configuration sheet
1