Appendix
B-10
2661
ANSI Curve
Backup overcurrent Inverse
Short Inverse
Long Inverse
Moderately Inverse
Very Inverse
Extremely Inverse
Definite Inverse
Inverse
ANSI Curve
2670
I(3I0)p Tele/BI
Backup overcurrent NO
YES
NO
Instantaneous trip via Teleprot./BI
2671
I(3I0)p SOTF
Backup overcurrent NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
2680
SOTF Time DELAY Backup overcurrent 0.00..30.00 sec
0.00 sec
Trip time delay after SOTF
2901 MEASURE.
SUPERV
Measurement
Supervision
ON
OFF
ON
Measurement Supervision
2902
BALANCE U-LIMIT Measurement
Supervision
10..100 V
50 V
Voltage Threshold for Balance Moni-
toring
2903
BAL. FACTOR U
Measurement
Supervision
0.58..0.95
0.75
Balance Factor for Voltage Monitor
2904
BALANCE I LIMIT
Measurement
Supervision
0.10..1.00 A
0.50 A
Current Balance Monitor
2905
BAL. FACTOR I
Measurement
Supervision
0.10..0.95
0.50
Balance Factor for Current Monitor
2906
Σ
I THRESHOLD
Measurement
Supervision
0.05..2.00 A
0.10 A
Summated Current Monitoring Thresh-
old
2907
Σ
I
FACTOR Measurement
Supervision
0.00..0.95
0.10
Summated Current Monitoring Factor
2910
FUSE FAIL MON.
Measurement
Supervision
ON
OFF
ON
Fuse Failure Monitor
2911 FFM
U>(min) Measurement
Supervision
10..100 V
30 V
Minimum Voltage Threshold U>
2912
FFM I< (max)
Measurement
Supervision
0.10..1.00 A
0.10 A
Maximum Current Threshold I<
2913
FFM U<max (3ph)
Measurement
Supervision
2..100 V
5 V
Maximum Voltage Threshold U<
(3phase)
2914
FFM Idelta (3p)
Measurement
Supervision
0.05..1.00 A
0.10 A
Delta Current Threshold (3phase)
2921
T mcb
Measurement
Supervision
0..30 ms
0 ms
T mcb
3101
FCT EarthFltO/C
Earth fault overcur-
rent
ON
OFF
ON
Earth Fault overcurrent function is
3102
BLOCK for Dist.
Earth fault overcur-
rent
with every Pickup
with single-phase Pickup
with multi-phase Pickup
NO
with every Pickup
Block E/F for Distance protection
3103
BLOCK 1pDeadTim Earth fault overcur-
rent
YES
NO
NO
Block E/F for 1pole Dead time
3104
Iph-STAB. Slope
Earth fault overcur-
rent
0..30 %
10 %
Stabilisation Slope with Iphase
3105
3IoMin Teleprot
Earth fault overcur-
rent
0.01..1.00 A
0.50 A
3Io-Min threshold for Teleprot.
schemes
3105
3IoMin Teleprot
Earth fault overcur-
rent
0.003..1.000 A
0.500 A
3Io-Min threshold for Teleprot.
schemes
3110
Op. mode 3I0>>>
Earth fault overcur-
rent
Forward
Reverse
Non-Directional
Inactive
Inactive Operating
mode
3111
3I0>>>
Earth fault overcur-
rent
0.50..25.00 A
4.00 A
3I0>>> Pickup
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...