Installation and Commissioning
8-22
7SA522 Manual
C53000-G1176-C119-2
8.2.2
Power Plant Connections
Before the device is energized for the first time, the device should be in the final oper-
ating environment for at least 2 hours to equalize the temperature and to minimize hu-
midity and avoid condensation. Connection are checked with the device at its final lo-
cation. The plant must first be switched off and grounded.
o
Protective switches (e.g. test switches, fuses, or miniature circuit breakers) for the
power supply and the measured voltages must be opened.
o
Check the continuity of all current and voltage transformer connections against the
system and connection diagrams:
q
Are the current transformers grounded properly?
q
Are the polarities of the current transformers the same?
q
Is the phase relationship of the current transformers correct?
q
Are the voltage transformers grounded properly?
q
Are the polarities of the voltage transformers correct?
q
Is the phase relationship of the voltage transformers correct?
q
Is the polarity for current input I
4
(if used) correct?
q
Is the polarity for voltage input U
4
correct (if used, e.g. with broken delta winding or
busbar voltage)?
o
Check the functions of all test switches that may be installed for the purposes of sec-
ondary testing and isolation of the device. Of particular importance are test switches
in current transformer circuits. Be sure these switches short-circuit the current trans-
formers when they are in the test mode (open).
o
The short-circuit feature of the current circuits of the device are to be checked. An
ohmmeter or other test equipment for checking continuity is needed.
q
Remove the front panel of the device (see Figure 8-7 or 8-8).
q
Remove the ribbon cable connected to the I/O–2 board (
ê
pull the board out until there is no contact between the board and the rear connec-
tions of the device.
q
At the terminals of the device, check continuity for each pair of terminals that re-
ceives current from the CTs.
Warning!
Some of the following test steps will be carried out in presence of hazardous voltages.
They shall be performed only by qualified personnel which is thoroughly familiar with
all safety regulations and precautionary measures and pay due attention to them.
Caution!
Operating the device on a battery charger without a connected battery can lead to un-
usually high voltages and consequently, the destruction of the device. For limit values
see Sub-section 10.2.1 under Technical Data.
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...