Appendix
B-17
7SA522 Manual
C53000-G1176-C119-2
3902
I> BF
Breaker Failure
0.05..20.00 A
0.10 A
Pick-up threshold I>
3903 1p-RETRIP
(T1) Breaker
Failure NO
YES
YES
1pole retrip with stage T1 (local trip)
3904
T1-1pole
Breaker Failure
0.00..30.00 sec
0.00 sec
T1, Delay after 1pole start (local trip)
3905
T1-3pole
Breaker Failure
0.00..30.00 sec
0.00 sec
T1, Delay after 3pole start (local trip)
3906
T2
Breaker Failure
0.00..30.00 sec
0.15 sec
T2, Delay of 2nd stage (busbar trip)
3907
T3-BkrDefective
Breaker Failure
0.00..30.00 sec
0.00 sec
T3, Delay for start with defective bkr.
3908
Trip BkrDefect.
Breaker Failure
NO
trips with T1-trip-signal
trips with T2-trip-signal
trips with T1 and T2-trip-sig-
nal
NO
Trip output selection with defective bkr
3909
Chk BRK CON-
TACT
Breaker Failure
NO
YES
YES
Check Breaker contacts
3921
End Flt. stage
Breaker Failure
ON
OFF
OFF
End fault stage is
3922
T-EndFault
Breaker Failure
0.00..30.00 sec
2.00 sec
Trip delay of end fault stage
3931 PoleDiscrepancy
Breaker
Failure ON
OFF
OFF
Pole Discrepancy supervision
3932
T-PoleDiscrep.
Breaker Failure
0.00..30.00 sec
2.00 sec
Trip delay with pole discrepancy
4001
FCT TripSuperv.
Trip Circuit Supervi-
sion
ON
OFF
OFF
TRIP Circuit Supervision is
4002
No. of BI
Trip Circuit Supervi-
sion
1..2
2
Number of Binary Inputs per trip circuit
4003
Alarm Delay
Trip Circuit Supervi-
sion
1..30 sec
2 sec
Delay Time for alarm
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...