Functions
6-226
7SA522 Manual
C53000-G1176-C119-2
6.16.2 Applying the Function Parameter Settings
The sensitivity of the measured value monitoring can be changed. In the factory, pre-
settings based on experience have already been applied, which should be sufficient
for most applications. If particularly high operational asymmetries of the currents and/
or voltages are expected, or if one or more monitoring functions pick up sporadically
during normal operation, the sensitivity setting(s) should be reduced.
In address
the measured value monitoring can be switched
21
or
2))
.
Symmetry
Monitoring
Address
determines the voltage threshold (phase–phase),
above which the voltage symmetry monitoring is in service (refer to Figure 6-116). Ad-
dress
is the corresponding symmetry factor, i.e. the slope of
the symmetry characteristic (Figure 6-116).
Address
determines the current threshold above which the
current symmetry monitoring is in service (refer also to Figure 6-115). Address
is the corresponding symmetry factor, i.e. the slope of the symmetry
characteristic (Figure 6-115).
Summation
Monitoring
Address
SI THRESHOLD determines the current threshold above which the cur-
rent summation monitoring (refer to Figure 6-114) picks up (absolute value, only re-
ferred to I
N
). The relative component (referred to the maximum conductor current) for
the pick-up of the current summation monitoring (Figure 6-114) is set in address
Voltage sum
internal (measured value
acquisition)
“
)DLO
Σ
83K(
” (165) general alarms: 164, 160 as allocated
Voltage symmetry
external (primary plant or
voltage transformers)
“
)DLO8EDODQFH
”
(167)
general alarms: 164, 160 as allocated
Voltage phase rotation
Extrem (primary plant or
connection)
“
)DLO3K6HT
”
(171)
general alarm: 160
as allocated
Voltage failure,
three-phase,
Fuse failure monitor
external (primary plant or
connection)
“
)XVH²)DLOXUH
” (169,
170)
general alarm: 160
distance protection
blocked
as allocated
Voltage failure,
single-/two-phase,
Fuse failure monitor
external (voltage transform-
ers)
“
)XVH²)DLOXUH
” (169,
170)
general alarm: 160
distance protection
blocked
as allocated
Trip circuit supervision
external (trip circuit or
control voltage failure)
“
)$,/7ULSFLU
”
(6865)
general alarm: –
as allocated
Table 6-6
Summary of the device response to detected failures
Monitoring
Possible causes
Alarm (function no.)
Failure response
General alarms
Output
1
) Following three unsuccessful reboot attempts, the device is taken out of service
2
) D.OK = “Device Okay” = Live contact relay
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...