Functions
6-176
7SA522 Manual
C53000-G1176-C119-2
3463
2.AR 1p allowed
YES
NO
NO
1pole TRIP allowed
3464
2.AR Tdead 1Flt
0.01..1800.00 sec
1.20 sec
Dead time after 1phase faults
3465
2.AR Tdead 2Flt
0.01..1800.00 sec
1.20 sec
Dead time after 2phase faults
3466
2.AR Tdead 3Flt
0.01..1800.00 sec
0.50 sec
Dead time after 3phase faults
3467
2.AR Tdead1Trip
0.01..1800.00 sec
1.20 sec
Dead time after 1pole trip
3468
2.AR Tdead3Trip
0.01..1800.00 sec
0.50 sec
Dead time after 3pole trip
3469
2.AR: Tdead EV.
0.01..1800.00 sec
1.20 sec
Dead time after evolving fault
3470
2.AR: CB? CLOSE
YES
NO
NO
CB ready interrogation before
reclosing
3471
2.AR SynRequest
YES
NO
NO
Request for synchro-check after
3pole AR
3472
3.AR: START
YES
NO
NO
AR start allowed in this cycle
3473
3.AR: T-ACTION
0.01..300.00 sec
0.20 sec
Action time
3474
3.AR 1p allowed
YES
NO
NO
1pole TRIP allowed
3475
3.AR Tdead 1Flt
0.01..1800.00 sec
1.20 sec
Dead time after 1phase faults
3476
3.AR Tdead 2Flt
0.01..1800.00 sec
1.20 sec
Dead time after 2phase faults
3477
3.AR Tdead 3Flt
0.01..1800.00 sec
0.50 sec
Dead time after 3phase faults
3478
3.AR Tdead1Trip
0.01..1800.00 sec
1.20 sec
Dead time after 1pole trip
3479
3.AR Tdead3Trip
0.01..1800.00 sec
0.50 sec
Dead time after 3pole trip
3480
3.AR: Tdead EV.
0.01..1800.00 sec
1.20 sec
Dead time after evolving fault
3481
3.AR: CB? CLOSE
YES
NO
NO
CB ready interrogation before
reclosing
3482
3.AR SynRequest
YES
NO
NO
Request for synchro-check after
3pole AR
3483
4.AR: START
YES
NO
NO
AR start allowed in this cycle
3484
4.AR: T-ACTION
0.01..300.00 sec
0.20 sec
Action time
3485
4.AR 1p allowed
YES
NO
NO
1pole TRIP allowed
3486
4.AR Tdead 1Flt
0.01..1800.00 sec
1.20 sec
Dead time after 1phase faults
3487
4.AR Tdead 2Flt
0.01..1800.00 sec
1.20 sec
Dead time after 2phase faults
3488
4.AR Tdead 3Flt
0.01..1800.00 sec
0.50 sec
Dead time after 3phase faults
3489
4.AR Tdead1Trip
0.01..1800.00 sec
1.20 sec
Dead time after 1pole trip
3490
4.AR Tdead3Trip
0.01..1800.00 sec
0.50 sec
Dead time after 3pole trip
3491
4.AR: Tdead EV.
0.01..1800.00 sec
1.20 sec
Dead time after evolving fault
3492
4.AR: CB? CLOSE
YES
NO
NO
CB ready interrogation before
reclosing
Addr.
Setting Title
Setting Options
Default Setting
Comments
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...