Appendix
B-5
7SA522 Manual
C53000-G1176-C119-2
1130
PoleOpenCurrent
Power System Data
2
0.05..1.00 A
0.10 A
Pole Open Current Threshold
1131
PoleOpenVoltage
Power System Data
2
2..70 V
30 V
Pole Open Voltage Threshold
1132
SI Time all Cl.
Power System Data
2
0.01..30.00 sec
0.05 sec
Seal-in Time after ALL closures
1134
Line Closure
Power System Data
2
Manual Close BI only
Current OR Voltage or Man-
ual close BI
CBaux OR Current or Man-
ual close BI
Current flow or Manual close
BI
Manual Close BI only
Recognition of Line Closures with
1135
Reset Trip CMD
Power System Data
2
with Pole Open Current
Threshold only
with CBaux AND Pole Open
Current
with Pole Open Current
Threshold only
RESET of Trip Command
1140
I-CTsat. Thres.
Power System Data
2
0.2..50.0 A
10.0 A
CT Saturation Threshold
1150
SI Time Man.Cl
Power System Data
2
0.01..30.00 sec
0.30 sec
Seal-in Time after MANUAL closures
1151
SYN.MAN.CL
Power System Data
2
with Synchronism-check
without Synchronism-check
NO
without Synchronism-check Manual CLOSE COMMAND genera-
tion
1155
3pole coupling
Power System Data
2
with Pickup
with Trip
with Trip
3 pole coupling
1156
Trip2phFlt
Power System Data
2
3pole
1pole, leading phase
1pole, lagging phase
3pole
Trip type with 2phase faults
1201
FCT Distance
Distance protec-
tion, general set-
tings
ON
OFF
ON
Distance protection is
1202
Minimum Iph>
Distance protec-
tion, general set-
tings
0.10..4.00 A
0.10 A
Phase Current threshold for dist.
meas.
1203
3I0> Threshold
Distance protec-
tion, general set-
tings
0.05..4.00 A
0.10 A
3I0 threshold for neutral current pickup
1204
3U0> Threshold
Distance protec-
tion, general set-
tings
1..100 V
5 V
3U0 threshold zero seq. voltage pickup
1207
3I0>/ Iphmax
Distance protec-
tion, general set-
tings
0.05..0.30
0.10
3I0>-pickup-stabilisation (3I0> /Iph-
max)
1215
Paral.Line Comp
Distance protec-
tion, general set-
tings
NO
YES
NO
Mutual coupling parall.line compensa-
tion
1221
2Ph-E faults
Distance protec-
tion, general set-
tings
block leading ph-e loop
block lagging ph-e loop
all loops
only phase-phase loops
only phase-earth loops
block leading ph-e loop
Loop selection with 2Ph-E faults
1232
SOTF zone
Distance protec-
tion, general set-
tings
with Pickup (non-directional)
with Zone Z1B
Inactive
Inactive
Instantaneous trip after SwitchOnTo-
Fault
1241
R load (Ø-E)
Distance protec-
tion, general set-
tings
0.10..250.00 Ohm
1
; Ohm
R load, minimum Load Impedance (ph-
e)
1242
ϕ
load (Ø-E)
Distance protec-
tion, general set-
tings
20..60
°
45
°
PHI load, maximum Load Angle (ph-e)
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...