Functions
6-147
7SA522 Manual
C53000-G1176-C119-2
The indicated secondary current values for setting ranges and default settings refer to
I
N
= 1 A. For the nominal current 5 A these values are to be multiplied by 5.
6.9.4
Information Overview
2660
IEC Curve
Normal Inverse
Very Inverse
Extremely Inverse
Long time inverse
Normal Inverse
IEC Curve
2661
ANSI Curve
Inverse
Short Inverse
Long Inverse
Moderately Inverse
Very Inverse
Extremely Inverse
Definite Inverse
Inverse
ANSI Curve
2662
LOG Curve
Logarithmic inverse
Logarithmic
inverse
LOG Curve
2670
I(3I0)p Tele/BI
NO
YES
NO
Instantaneous trip via Teleprot./
BI
2671
I(3I0)p SOTF
NO
YES
NO
Instantaneous trip after Swit-
chOnToFault
2630
Iph> STUB
0.10..25.00 A
0.50 A
Iph> STUB Pickup
2631
T Iph STUB
0.00..30.00 sec
0.00 sec
T Iph STUB Time delay
2632
3I0> STUB
0.05..25.00 A
0.20 A
3I0> STUB Pickup
2633
T 3I0 STUB
0.00..30.00 sec
0.00 sec
T 3I0 STUB Time delay
2634
I-STUB Telep/BI
NO
YES
NO
Instantaneous trip via Teleprot./
BI
2635
I-STUB SOTF
NO
YES
NO
Instantaneous trip after Swit-
chOnToFault
Addr.
Setting Title
Setting Options
Default Setting
Comments
F.No.
Alarm
Comments
7104
>BLOCK O/C I>>
>BLOCK Backup OverCurrent I>>
7105
>BLOCK O/C I>
>BLOCK Backup OverCurrent I>
7106
>BLOCK O/C Ip
>BLOCK Backup OverCurrent Ip
7110
>O/C InstTRIP
>Backup OverCurrent InstantaneousTrip
7130
>BLOCK I-STUB
>BLOCK I-STUB
7131
>I-STUB ENABLE
>Enable I-STUB-Bus function
7151
O/C OFF
Backup O/C is switched OFF
7152
O/C BLOCK
Backup O/C is BLOCKED
7153
O/C ACTIVE
Backup O/C is ACTIVE
7161
O/C PICKUP
Backup O/C PICKED UP
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...