Functions
6-115
7SA522 Manual
C53000-G1176-C119-2
Sequence
Figure 6-66 shows the logic diagram of the directional comparison scheme for one line
end.
The directional comparison only functions for faults in the “forward” direction. Accord-
ingly the over current stage intended for operation in the direction comparison mode
must definitely be set to
)RUZDUG
(
,',5(&7,21
); refer also to Sub-section
6.5.2 under the margin heading “Teleprotection with Earth Fault Protection”.
On three terminal lines, the send signal is routed to both opposite line ends. The re-
ceive signals are then combined with a logical
AND
gate, as all three line ends must
transmit a send signal during an internal fault. Via the setting parameter
(address
), the device is informed as to whether it has one or two opposite
line ends.
The occurrence of erroneous signals resulting from transients during clearance of ex-
ternal faults or from direction reversal resulting during the clearance of faults on par-
allel lines, is neutralized by the “Transient Blocking” (refer to Sub-section 6.6.1.4).
On feeders with only a single-sided infeed or where the star-point is only earthed be-
hind one line end, the line end without zero sequence current cannot generate a per-
missive signal, as fault detection does not take place there. To ensure tripping by the
directional comparison even in this case the device contains a special function. This
“Weak Infeed Function” (echo function) is referred to in Sub-section 6.6.1.5. It is acti-
vated when a signal is received from the opposite line end — in the case of three ter-
minal lines from at least one of the opposite line ends — without the device having de-
tected a fault.
The circuit breaker can also be tripped at the line end with no or only weak infeed. This
“Weak-Infeed Tripping” is referred to in Section 6.7.
Figure 6-66 Logic diagram of the directional comparison scheme (one line end)
Two terminals
EF Telep. off
EF Pickup
&
EF forward
6HQG3URORQJ
T
0
&
EF Enable Trip
Three terminals
Two terminals
Three terminals
„1“
/LQH&RQILJ
≥
1
&
Trip command
&
Transient blocking
≥
1
&
≥
1
EF TeleprotOFF
≥
1
&
≥
1
Echo function
section 6.6.1.5
weak infeed trip
1313 >EF TeleprotBLK
1381
1318 >EF Rec.Ch1
1319 >EF Rec.Ch2
EF Tele SEND
1384
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...