Hardware and Connections
2-13
7SA522 Manual
C53000-G1176-C119-2
2.1.4
Connections to Optical Communication Interfaces
Optical
Communication
Interfaces
The three available versions of optical communication interfaces are shown in Figure
2-14. The ports are supplied with caps to protect the optical components against dust
or other contaminants. The caps can be removed by turning them 90° to the left.
Figure 2-14
Optical communication interfaces with protective caps
Connections to
Optical
Communication
Interfaces
Optical connector type:
ST–connector
Fibre type:
Multimode graded-index (“G”) optical fibre
G50/125 µm,
G62.5/125 µm,
G100/140 µm
Wavelength:
λ
= 820 nm (approximately)
Allowable bending radius:
For indoor cable
r
min
= 5 cm (2 in)
For outdoor cable r
min
= 20 cm (8 in)
Laser class 1 (acc. EN 60825–1) is achieved with fibre type G50/125 µm and
G62.5/125 µm.
2 channel
1 channel
Ch
1
P-
S
la
ve
Ch
2
P-
M
as
te
r
U
ART
Ch
1
P-
S
la
ve
AM
O
1 channel