Functions
6-227
7SA522 Manual
C53000-G1176-C119-2
Fuse Failure
Monitor
(Non-Symmetrical
Voltages)
The settings of the fuse failure monitor for non-symmetrical measured voltage failure
(single- or two-phase) must be selected such that on the one hand reliable pick-up of
the monitoring is ensured in the case of loss of a single-phase voltage (address
), while on the other hand a pick-up due to earth faults in an earthed
system is avoided. In accordance with this requirement, address
must be set sufficiently sensitive (below the smallest fault current due to earth
faults). In address
, the fuse failure monitor can be switched
2))
e.g. during non symmetrical testing.
Fuse Failure
Monitor
(Three-Phase)
In address
the minimum voltage threshold is set. If the
measured voltage drops below this threshold and a simultaneous current jump which
exceeds the limits according to address
is not detected
while all three phase currents are greater than the minimum current required for the
impedance measurement by the distance protection according to address
, a three phase measured voltage failure is recognized.
Circuit Breaker
for Voltage
Transformers
If a circuit breaker for voltage transformers (VT mcb) is installed in the secondary cir-
cuit of the voltage transformers, the status is sent, via binary input, to the device
informing it about the position of the VT mcb. If a short-circuit in the secondary side
initiates the tripping of the VT mcb, the distance protection function has to be blocked
immediately. Otherwise a trip by the distance protection due to the lack of measured
voltage while load current is on. The blocking must be faster than the first stage of the
distance protection.This requires an extremely short reaction time for VT mcb (
≤
4 ms
for 50 Hz,
≤
3 ms for 60 Hz nominal frequency). If this cannot be ensured, the reac-
tion time is to be set under address
Note
that the fast trip of Zone 1 is delayed by the setting in
. Unless absolutely
necessary the setting should be zero. Altenatively the intenal Fuse Failure Monitor can
be used (see above).
Trip Circuit
Supervision
The number of circuits to be monitored was set during the configuration in address
7ULS&LUF6XSHUY
(Section 5.1). If the trip circuit supervision is not used at all,
the setting
'LVDEOHG
must be applied there.
The trip circuit supervision can be switched
21
or
2))
in address
. The number
of binary inputs that shall be used in each of the monitored circuits is set in address
If the marshalling of the binary inputs required for this function
does not correspond to the previously selected type of monitoring, a corresponding
alarm is issued (“
7ULS&3URJ)$,/
” with the number of the faulty monitoring circuit).
The trip circuit failure alarm is delayed by a fixed period of approximately 1 s to 2 s in
the case of monitoring with two binary inputs. The alarm delay in the event of monitor-
ing with one binary input can be set in address
$ODUP'HOD\
. If 7SA522 is the
only device connected in the trip circuit, a delay of 1 s to 2 s is sufficient as the trip
circuit supervision is not active during a detected system fault. If, however, trip con-
tacts from other devices are connected in parallel in the trip circuit, the fail alarm must
be delayed such that the longest trip command duration can be reliably bridged.
Note:
The current summation monitoring is only in service if the earth current of the protect-
ed feeder is connected to the fourth current measuring input (
I
4
) for earth currents.
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...