Appendix
B-6
1243
R load (Ø-Ø)
Distance protec-
tion, general set-
tings
0.10..250.00 Ohm
1
; Ohm
R load, minimum Load Impedance (ph-
ph)
1244
ϕ
load (Ø-Ø)
Distance protec-
tion, general set-
tings
20..60
°
45
°
PHI load, maximum Load Angle (ph-
ph)
1301
Op. mode Z1
Distance zones
(quadrilateral)
Forward
Reverse
Non-Directional
Inactive
Forward
Operating mode Z1
1302
R(Z1) Ø-Ø
Distance zones
(quadrilateral)
0.05..250.00 Ohm
1.25 Ohm
R(Z1), Resistance for ph-ph-faults
1303
X(Z1)
Distance zones
(quadrilateral)
0.05..250.00 Ohm
2.50 Ohm
X(Z1), Reactance
1304
RE(Z1) Ø-E
Distance zones
(quadrilateral)
0.05..250.00 Ohm
2.50 Ohm
RE(Z1), Resistance for ph-e faults
1305
T1-1phase
Distance zones
(quadrilateral)
0.00..30.00 sec
0.00 sec
T1-1phase, delay for single phase
faults
1305
T1-1phase
Distance zones (
MHO)
0.00..30.00 sec
0.00 sec
T1-1phase, delay for single phase
faults
1306
T1-multi-phase
Distance protec-
tion, general set-
tings
0.00..30.00 sec
0.00 sec
T1multi-ph, delay for multi phase faults
1306
T1-multi-phase
Distance zones
(quadrilateral)
0.00..30.00 sec
0.00 sec
T1multi-ph, delay for multi phase faults
1306
T1-multi-phase
Distance zones (
MHO)
0.00..30.00 sec
0.00 sec
T1multi-ph, delay for multi phase faults
1307
Zone Reduction
Distance zones
(quadrilateral)
0..30
°
0
°
Zone Reduction Angle (load compen-
sation)
1311
Op. mode Z2
Distance zones
(quadrilateral)
Forward
Reverse
Non-Directional
Inactive
Forward
Operating mode Z2
1312
R(Z2) Ø-Ø
Distance zones
(quadrilateral)
0.05..250.00 Ohm
2.50 Ohm
R(Z2), Resistance for ph-ph-faults
1313
X(Z2)
Distance zones
(quadrilateral)
0.05..250.00 Ohm
5.00 Ohm
X(Z2), Reactance
1314
RE(Z2) Ø-E
Distance zones
(quadrilateral)
0.05..250.00 Ohm
5.00 Ohm
RE(Z2), Resistance for ph-e faults
1315
T2-1phase
Distance zones
(quadrilateral)
0.00..30.00 sec
0.30 sec
T2-1phase, delay for single phase
faults
1315
T2-1phase
Distance zones (
MHO)
0.00..30.00 sec
0.30 sec
T2-1phase, delay for single phase
faults
1316
T2-multi-phase
Distance zones
(quadrilateral)
0.00..30.00 sec
0.30 sec
T2multi-ph, delay for multi phase faults
1316
T2-multi-phase
Distance zones (
MHO)
0.00..30.00 sec
0.30 sec
T2multi-ph, delay for multi phase faults
1317
Trip 1pole Z2
Distance zones
(quadrilateral)
NO
YES
NO
Single pole trip for faults in Z2
1317
Trip 1pole Z2
Distance zones (
MHO)
NO
YES
NO
Single pole trip for faults in Z2
1321
Op. mode Z3
Distance zones
(quadrilateral)
Forward
Reverse
Non-Directional
Inactive
Reverse
Operating mode Z3
1322
R(Z3) Ø-Ø
Distance zones
(quadrilateral)
0.05..250.00 Ohm
5.00 Ohm
R(Z3), Resistance for ph-ph-faults
1323
X(Z3)
Distance zones
(quadrilateral)
0.05..250.00 Ohm
10.00 Ohm
X(Z3), Reactance
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...