Functions
6-7
7SA522 Manual
C53000-G1176-C119-2
6.1.1
Power System Data 1
Some system and plant data are required by the device, so that it may adapt its func-
tions to these data, according to its mode of operation. Amongst others, the plant and
instrument transformer ratings, polarity and termination of the measured values, pa-
rameters of the circuit breaker, etc. These data are summarized in
If the key
is operated, the main menu is displayed. With the key
the option
6HW
WLQJV
is selected and by pushing the key
the selection of
6HWWLQJV
is con-
firmed. To enter the plant data
must
be selected in the menu
6HWWLQJV
.
With DIGSI
®
4 the corresponding selection is reached by double click on
Polarity of Current
Transformers
In address
the polarity of the current transformers must be en-
tered, in other words, the location of the CT star-point (Figure 6-8). This setting deter-
mines the measuring direction of the device (forward = line direction). A change of this
parameter also results in the polarity reversal of the earth current input.
Figure 6-8 Current transformer polarity
Instrument Trans-
former Nominal
Values
In the address
the device is in-
formed of the primary and secondary rated voltage (line voltage) of the voltage trans-
formers. In the address
the primary
and secondary rated current (phase current) of the current transformers are entered.
Please observe that the rated current transformer secondary current must corre-
sponds to the rated current of the device, as the device would otherwise compute in-
correct primary data.
Correct entry of the primary data is a prerequisite for the correct computation of oper-
ational measured values with primary magnitude. If DIGSI
®
4 is used to enter param-
eters as primary quantities, the correct entry of the primary data is an important pre-
requisite for the correct operation of the device.
Voltage Trans-
former Connection
The device contains four voltage measuring inputs, three of which are connected to
the set of voltage transformers. For the fourth voltage transformer U
4
input several op-
tions are available:
•
Connection of the U
4
input to the open delta connection e–n of a set of voltage
transformers, refer to appendix A, Figure 1-14:
Address
is then set to:
8GHOWDWUDQVI
.
MENU
I
L1
I
L2
I
L3
I
N
I
L1
I
L2
I
L3
I
N
%XV
$GGUHVV
WRZDUGV/LQH
/LQH
/LQH
$GGUHVV
WRZDUGV%XVEDU
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...