Functions
6-54
7SA522 Manual
C53000-G1176-C119-2
Zone Z1B is usually used in combination with automatic reclosure and/or teleprotec-
tion systems. It can be activated internally by the teleprotection functions (see also
section 6.4) or the integrated automatic reclosure (if available, see also section 6.1) or
externally by a binary input. It is generally set to at least 120% of the line length. On
three-terminal line applications (teed feeders), it must be set to securely reach beyond
the longest line section, even when there is additional infeed via the tee-off point. The
delay times are set in accordance with the type of application, usually to zero or a very
small delay. When used in conjunction with teleprotection comparison systems, the
dependence on the fault detection must be considered (refer to margin heading “Dis-
tance Protection Prerequisites” in Sub-section 6.4.2.
If the distance protection is used in conjunction with an automatic recloser, it may be
determined in address 1357
which distance zones are released prior
to a rapid automatic reclosure. Usually the overreaching zone Z1B is used for the first
cycle (
<HV
). This may be suppressed by changing the setting to
equals
1R
. In this case the overreaching zone Z1B is not released
before and during the 1
st
automatic reclose cycle. Zone Z1 is always released. The
setting only has an effect when the service condition of the automatic reclose function
is input to the device via binary input “>Enable ARzones” (FNo. 383, power system
data 2).
6.2.3.3
Settings
Addr.
Setting Title
Setting Options
Default Setting
Comments
1301
Op. mode Z1
Forward
Reverse
Non-Directional
Inactive
Forward
Operating mode Z1
1302
R(Z1) Ø-Ø
0.05..250.00 Ohm
1.25 Ohm
R(Z1), Resistance for ph-ph-
faults
1303
X(Z1)
0.05..250.00 Ohm
2.50 Ohm
X(Z1), Reactance
1304
RE(Z1) Ø-E
0.05..250.00 Ohm
2.50 Ohm
RE(Z1), Resistance for ph-e
faults
1305
T1-1phase
0.00..30.00 sec
0.00 sec
T1-1phase, delay for single
phase faults
1306
T1-multi-phase
0.00..30.00 sec
0.00 sec
T1multi-ph, delay for multi phase
faults
1307
Zone Reduction
0..30
°
0
°
Zone Reduction Angle (load
compensation)
1351
Op. mode Z1B
Forward
Reverse
Non-Directional
Inactive
Forward
Operating mode Z1B (overrre-
ach zone)
1352
R(Z1B) Ø-Ø
0.05..250.00 Ohm
1.50 Ohm
R(Z1B), Resistance for ph-ph-
faults
1353
X(Z1B)
0.05..250.00 Ohm
3.00 Ohm
X(Z1B), Reactance
1354
RE(Z1B) Ø-E
0.05..250.00 Ohm
3.00 Ohm
RE(Z1B), Resistance for ph-e
faults
1355
T1B-1phase
0.00..30.00 sec
0.00 sec
T1B-1phase, delay for single ph.
faults
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...