Functions
6-165
7SA522 Manual
C53000-G1176-C119-2
If
only
three-pole reclose cycles are to be executed, it is sufficient to assign the binary
input "
) for the trip signal. Figure 6-89 shows an
example. The overreaching stages of the external protection are again enabled by
"
" (F.No
) and if applicable by further cycles.
Figure 6-88 Connection example with external protection device for 1-/3-pole reclosure;
AR control mode =
ZLWK3,&.83
Figure 6-89 Connection example with external protection device for 3-pole reclosure;
AR control mode =
ZLWK75,3
If, on the other hand, the internal automatic reclosure function is controlled by the
pickup (only possible with three-pole tripping:
7ULSPRGH SROHRQO\
, the
phase-segragated start signals must be connected from the external protection. The
general trip command then suffices for tripping (F.No
). Figure 6-90 shows con-
nection examples.
7SA522
AR Start
Tripping L1
Tripping L2
Tripping L3
L+
external
protection device
Relay Pickup
3-phase coupling
L–
L–
L–
only 1-pole
(if nec. for other AR)
7SA522
trip
Tripping
L+
external
protection device
Relay Pickup
L–
L–
L+
(if nec. for other AR)
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...