Functions
6-98
7SA522 Manual
C53000-G1176-C119-2
Definite Time Very
High Set Current
Stage 3I
0
>>>
The earth current I
E
is passed through a numerical filter and then compared with the
set value
. If this value is exceeded and alarm is issued. After the correspond-
ing delay times
have expired, a trip command is issued which is also
alarmed. The reset threshold is approximately 5 % + 0,5 mA below the pick-up thresh-
old.
The possibilities of intervention are referred to in the heading “General”. Figure 6-57
shows the logic diagram of the 3I
0
>>>–stage. The function modules “direction deter-
mination”, “permissive teleprotection”, “switch onto fault”, and “inrush stabilization” are
common to all stages and described below. They may however affect each stage in-
dividually. This is done with the following parameters:
•
, determines the operating direction of the stage:
)RUZDUG
,
5HYHUVH
or
1RQ'LUHFWLRQDO
,
•
, determines whether a non-delayed trip with the teleprotection
scheme is possible (
<HV
) or not possible (
1R
),
•
, determines whether during energization of the feeder onto a
fault tripping with this stage shall be non-delayed (
<HV
) or not (
1R
) and
•
, which is used to switch the inrush stabilization (rush blocking)
on (
<HV
) or off (
1R
).
Figure 6-57
Logic diagram of the 3I
0
>>>–stage
Definite Time High
Set Current
Stage 3I
0
>>
The logic of the high set current stage 3I
0
>> is the same as that of the 3I
0
>>>–stage.
In all references 3I0>>> must merely be replaced by
also applies.
Definite Time
Overcurrent
Stage 3I
0
>
The logic of the overcurrent stage 3I
0
> is the same as that of the 3I
0
>>>–stage. In all
references 3I0>>> must merely be replaced with
applies. A fourth, definite time stage can be implemented by setting the “inverse” stage
(refer to the next paragraph) to a definite time stage.
I
E
3I
0
>>>
Yes
No
Reverse
Forward
Non-Direct.
„1“
≥
1
&
&
inrush-
stabilization
direction-
determination
forwards
reverse
&
&
Yes
No
,!!!627)7ULS
Yes
No
permissive
teleprot..
switch onto
fault
≥
1
EF 3I0>>> TRIP
T
0
7627)7LPH'(/$<
T
0
&
&
PICKUP
DIRECT.
&
627)2S0RGH
1305 >EF BLK 3I0>>>
1354 EF 3I0>>>Pickup
1366
,!!!,QUXVK%ON
,!!!7HOHS%,
≥
1
>EF Inst TRIP
Inactive
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...