Appendix
B-9
7SA522 Manual
C53000-G1176-C119-2
2404 I>>>
Instantaneous
High-
Speed SOTF Over-
current
1.00..25.00 A
2.50 A
I>>> Pickup
2501
FCT Weak Infeed
Weak Infeed (Trip
and/or Echo)
OFF
Echo only
Echo and Trip
Echo only
Weak Infeed function is
2502
Trip/Echo DELAY
Weak Infeed (Trip
and/or Echo)
0.00..30.00 sec
0.04 sec
Trip / Echo Delay after carrier receipt
2503
Trip EXTENSION
Weak Infeed (Trip
and/or Echo)
0.00..30.00 sec
0.05 sec
Trip Extension / Echo Impulse time
2505
UNDERVOLTAGE Weak Infeed (Trip
and/or Echo)
2..70 V
25 V
Undervoltage (ph-e)
2601
Operating Mode
Backup overcurrent ON
Only Active with Loss of VT
sec. circuit
OFF
Only Active with Loss of VT
sec. circuit
Operating mode
2610
Iph>>
Backup overcurrent 0.10..25.00 A
2.00 A
Iph>> Pickup
2611
T Iph>>
Backup overcurrent 0.00..30.00 sec
0.30 sec
T Iph>> Time delay
2612
3I0>> PICKUP
Backup overcurrent 0.05..25.00 A
0.50 A
3I0>> Pickup
2613
T 3I0>>
Backup overcurrent 0.00..30.00 sec
0.30 sec
T 3I0>> Time delay
2614
I>>
Telep/BI Backup
overcurrent
NO
YES
YES
Instantaneous trip via Teleprot./BI
2615
I>>
SOTF Backup
overcurrent
NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
2620
Iph>
Backup overcurrent 0.10..25.00 A
1.50 A
Iph> Pickup
2621
T Iph>
Backup overcurrent 0.00..30.00 sec
0.50 sec
T Iph> Time delay
2622
3I0>
Backup overcurrent 0.05..25.00 A
0.20 A
3I0> Pickup
2623
T 3I0>
Backup overcurrent 0.00..30.00 sec
0.50 sec
T 3I0> Time delay
2624
I> Telep/BI
Backup overcurrent NO
YES
NO
Instantaneous trip via Teleprot./BI
2625
I> SOTF
Backup overcurrent NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
2630
Iph> STUB
Backup overcurrent 0.10..25.00 A
0.50 A
Iph> STUB Pickup
2631
T Iph STUB
Backup overcurrent 0.00..30.00 sec
0.00 sec
T Iph STUB Time delay
2632
3I0> STUB
Backup overcurrent 0.05..25.00 A
0.20 A
3I0> STUB Pickup
2633
T 3I0 STUB
Backup overcurrent 0.00..30.00 sec
0.00 sec
T 3I0 STUB Time delay
2634
I-STUB Telep/BI
Backup overcurrent NO
YES
NO
Instantaneous trip via Teleprot./BI
2635
I-STUB SOTF
Backup overcurrent NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
2640
Ip>
Backup overcurrent 0.10..4.00 A
∞
A
Ip> Pickup
2642
T Ip Time Dial
Backup overcurrent 0.05..3.00 sec
0.50 sec
T Ip Time Dial
2643
Time Dial TD Ip
Backup overcurrent 0.50..15.00
5.00
Time Dial TD Ip
2646
T Ip Add
Backup overcurrent 0.00..30.00 sec
0.00 sec
T Ip Additional Time Delay
2650
3I0p PICKUP
Backup overcurrent 0.05..4.00 A
∞
A
3I0p Pickup
2652
T 3I0p TimeDial
Backup overcurrent 0.05..3.00 sec
0.50 sec
T 3I0p Time Dial
2653
TimeDial TD3I0p
Backup overcurrent 0.50..15.00
5.00
Time Dial TD 3I0p
2656
T 3I0p Add
Backup overcurrent 0.00..30.00 sec
0.00 sec
T 3I0p Additional Time Delay
2660
IEC Curve
Backup overcurrent Normal Inverse
Very Inverse
Extremely Inverse
Long time inverse
Normal Inverse
IEC Curve
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...