Installation and Commissioning
8-41
7SA522 Manual
C53000-G1176-C119-2
Before the breaker is closed again for normal operation the trip command of the feeder
protection routed to the circuit breaker must be disconnected so that the trip command
can only be initiated by the breaker failure protection.
Although the following lists do not claim to be complete it may also contain points
which are to be ignored in the current application.
Circuit Breaker
Auxiliary Contacts
If the circuit breaker auxiliary contacts are connected to the device, these provide an
essential input to the functionality of the breaker failure protection. Make sure the
correct assignment has been checked (Section 8.3.4).
External Start
Conditions
If the breaker failure protection can also be started by external protection devices, the
external start conditions should be checked. Single-pole or three-pole tripping is pos-
sible depending on the setting of the breaker failure protection. The pole discrepancy
check of the device or the breaker may itself lead to three-pole tripping after single-
pole tripping. Therefore check first how the parameters of the breaker failure protec-
tion are set. See Subsection 6.15.2, addresses
onwards.
In order for the breaker failure protection to be started, a current must flow at least via
the monitored phase. This may be a secondary injected current.
After every start, the message "
" (FNo. 1461) must appear in the
spontaneous annunciation list or the trip log.
Only if single-pole starting possible:
q
single-pole starting by trip command of the external protection in phase L1:
binary input functions "
" and possibly "
" (in sponta-
neous or fault messages). Trip command depending on configuration.
q
single-pole starting by trip command of the external protection in phase L2:
binary input functions "
" and possibly "
" (in sponta-
neous or fault messages"). Trip command depending on configuration.
q
single-pole starting by trip command of external protection in phase L3:
binary input functions "
" and possibly "
" (in sponta-
neous or fault messages). Trip command depending on configuration.
q
three-pole starting by trip command of the external protection via all three binary in-
puts L1, L2 and L3:
binary input functions "
" and "
and possibly "
" (in spontaneous or fault messages). Trip command
three-pole.
For three-pole starting:
q
three-pole starting by trip command of the external protection:
binary input functions "
" and possibly "
" (in spon-
taneous or fault messages". Trip command depending on configuration.
Switch off test current.
If BF start is possible without current flow
q
BF start by trip command of the external protection without current flow:
binary input functions "
" (in spon-
taneous or fault messages). Trip command depending on configuration.
Busbar tripping
For testing the distribution of the trip commands in the substation in the case of
breaker failures it is important to check that the trip commands to the surrounding
circuit breakers is correct.
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...