Functions
6-124
7SA522 Manual
C53000-G1176-C119-2
The transient blocking time
(address
) must definitely be set
longer than the duration of severe transients resulting from the inception or clearance
of external faults. The transmit signal is delayed by this time in the case of the permis-
sive protection schemes
'LU&RPS3LFNXS
and
81%/2&.,1*
if the protection had
initially detected a reverse fault. In the case of the blocking scheme
%/2&.,1*
the re-
ceived (blocking) signal is prolonged by this time.
The preset value should be sufficient in most cases.
Echo Function
In the case of line ends with weak infeed, or not sufficient earth current, the echo func-
tion is sensible for the permissive scheme so that the infeeding line end can be re-
leased. The echo function may be activated under address
(
(&+2RQO\
) or deactivated (
2))
). With this “switch” it is also possible to activate the
weak infeed tripping (
(&+2DQG75,3
, refer also to Section 6.7).
The comments above regarding the setting of the current stage
(address
) must be noted as well as the margin heading “Earth Fault Protection
(address
) must be set long enough to
ensure that no unwanted echo signals are generated due to differences in the pick-up
times of the earth fault protection fault detection at the two line ends during external
faults (through-fault current). Typical setting is approx. 40 ms (presetting). This setting
can only be modified with DIGSI
®
4 under “Additional Settings”.
The echo impulse duration
(address
) may be matched to the
configuration data of the signal transmission equipment. It must be set long enough to
ensure that the received signal is reliably detected taking into consideration possible
differences in the operating times of the protection and transmission equipment at the
two line ends. In most cases approx. 50 ms (presetting) is sufficient. This setting can
only be modified with DIGSI
®
4 under “Additional Settings”.
The echo function settings are common to all weak infeed measures and summarized
in tabular form in Section 6.7.
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...