Functions
6-109
7SA522 Manual
C53000-G1176-C119-2
6.5.3
3101
OFF
ON
Earth Fault overcurrent
function is
3102
with every Pickup
with single-phase Pickup
with multi-phase Pickup
NO
with every Pickup
Block E/F for Distance protec-
tion
3103 BLOCK
YES
NO
NO
3104
Iph-STAB. Slope 0..30 %
10 %
Stabilisation Slope with
Iphase
3105
0.01..1.00 A
0.50 A
3Io-Min threshold for Teleprot.
schemes
3105
0.003..1.000 A
0.500 A
3Io-Min threshold for Teleprot.
schemes
3110 Op.
mode
3I0>>>
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3111
3I0>>>
0.50..25.00 A
4.00 A
3I0>>> Pickup
3112
T 3I0>>>
0.00..30.00 sec
0.30 sec
T 3I0>>> Time delay
3113
NO
YES
NO
Instantaneous trip via Tele-
prot./BI
3114 3I0>>>SOTF-
NO
YES
NO
Instantaneous trip after Swit-
chOnToFault
3115 3I0>>>InrushBlk NO
YES
NO
3120
Op. mode 3I0>>
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3121
3I0>>
0.20..25.00 A
2.00 A
3I0>> Pickup
3122
T 3I0>>
0.00..30.00 sec
0.60 sec
T 3I0>> Time Delay
3123 3I0>>
Telep/BI NO
YES
NO
Instantaneous trip via Tele-
prot./BI
3124 3I0>>
NO
YES
NO
Instantaneous trip after Swit-
chOnToFault
3125 3I0>>
InrushBlk NO
YES
NO
3130
Op. mode 3I0>
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3131
3I0>
0.05..25.00 A
1.00 A
3I0> Pickup
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...