Configuration
5-12
7SA522 Manual
C53000-G1176-C119-2
−
T
Trip Log Buffer in the Device,
−
S
System Interface,
−
C
CFC, Information is processed by CFC Program of the User-definable Logic.
−
CM
Control of switchgears if a switch plant is indicated in the Control Menu of
the device
5.2.3
Control Commands for switching devices
Control commands are output indications which are specially configured for the trans-
mission of control signals to power plant switching devices (circuit breakers, isolators,
etc.). Once the type of a command has been established, DIGSI
®
4 reserves a corre-
sponding number of output relay contacts. For this, the corresponding output relays
are numbered consecutively. This must be observed when wiring the relays to the cor-
responding power plant to be controlled.
Table 5-1 shows the most important command types. The following Figures 5-5
through 5-9 show time diagrams, control settings, and the order of relay positioning for
frequently used command types.
For double commands, the first output relay is selected using DIGSI
®
4. The other out-
put relays will be automatically selected by DIGSI
®
4. In the sequence of output relays,
each TRIP command is placed before the associated CLOSE command. For
commands with feedback indications, DIGSI
®
4 reserves another line in the configu-
ration matrix for the switching device feedback indications. Here, the OPEN position
feedback is placed before the CLOSED position feedback as well.
For Figures 5-5 through 5-9, the following abbreviations apply:
−
C+
Relay contact for closing
−
C–
Relay contact for tripping
−
CC
Relay contact is common
−
CCC
Relay contact is common to a bus
−
L+; L–
Control voltage
Table 5-1
Most important command types
Single Command with
Single Output
With 1 relay
without feedback
with feedback
&B6
&)B6
Double Command with
Single Outputs
With 2 relays
without feedback
with feedback
&B'
&)B'
Double Command with Single
Outputs plus Common Output
With 3 relays
without feedback
with feedback
&B'
&)B'
Double Command with Double
Outputs
With 4 relays
without feedback
with feedback
&B'
&)B'
Double Command with Double
(Close) and Single (Trip)
Outputs
With 3 relays
without feedback
with feedback
&B'
&)B'
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...