Alarms, faults and system messages
9.2 System runtime
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
435
Table 9- 4
Communication diagnostics via PROFIBUS DP
LED BF
Explanation
off
Cyclic data exchange (or PROFIBUS not used, p2030 = 0)
RED - slow
Bus fault - configuration fault
RED - fast
Bus fault
- no data exchange
- baud rate search
- no connection
YELLOW - variable
frequency
Firmware update in progress
LED BF display for CANopen
In addition to the signal states "on" and "off" there are three different flashing frequencies:
Table 9- 5
Communication diagnostics via CANopen
BF LED
Explanation
GREEN - on
Bus state "Operational"
GREEN - fast
Bus state "Pre-Operational"
GREEN - single flash Bus state "Stopped"
RED - on
No bus
RED - single flash
Alarm - limit reached
RED - double flash Error event in control (Error Control Event)
YELLOW - variable
frequency
Firmware update in progress
9.2
System runtime
By evaluating the system runtime of the inverter, you can decide when you should replace
components subject to wear in time before they fail - such as fans, motors and gear units.
Principle of operation
The system runtime is started as soon as the Control Unit power supply is switched-on.
The system runtime stops when the Control Unit is switched off.
The system runtime comprises r2114[0] (milliseconds) and r2114[1] (days):
System runtime = r2114[1] × days + r2114[0] × milliseconds
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......