Commissioning
5.5 Procedure for commissioning via STARTER
Inverter cabinet units
160
Operating Instructions, 12/2014, A5E32923362A
Default settings for setpoints/command sources
Figure 5-21 Default settings for setpoints/command sources
⇒
Select the preselection of the setpoints and command sources; the list of selection options
depends on the deployed Control Unit, see also Section Pre-assignment of inputs/outputs
and wiring via p0015 macros (Page 124):
●
No selection
●
7.) Fieldbus with data set switchover
●
9.) Standard I/O with MOP
●
12.) Standard I/O with analog setpoint
●
14.) Process industry with fieldbus
●
15.) Process industry
●
17.) 2-wire (forw/backw1)
●
18.) 2-wire (forw/backw2)
●
19.) 3-wire (enable/forw/backw)
●
20.) 3-wire (enable/on/reverse)
●
21.) USS fieldbus
●
22.) CAN fieldbus
⇒
Click on Continue >